Parameters
Switching operation mode by external signal (X16 signal)
● When External operation and the operation from the operation panel are used together, the PU
operation mode and External operation mode can be switched during a stop (during motor stop,
start command OFF) by using the PU-External operation switchover signal (X16).
● When Pr. 79 = "0", "6" or "7", switching between the PU operation mode and External operation
mode is possible. (When Pr. 79 = "6", the switchover can also be made during operation.)
● To input the X16 signal, set "16" in any of Pr. 178 to Pr. 189 (input terminal function selection) to
assign the function to a terminal.
Pr. 79
setting
0 (initial value)
7
Tab. 5-54:
NOTES
The status of the operation mode follows the Pr. 340 "Communication startup mode selection"
setting and the ON/OFF state of the X65 and X66 signals. (For details, refer to page 5-123.)
The priority among Pr. 79 and Pr. 340 and signals is Pr. 79 > X12 > X66 > X65 > X16 > Pr. 340.
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may
affect the other functions. Set parameters after confirming the function of each terminal.
Switching the operation mode by external signals (X65, X66 signals)
● When Pr. 79 = "0, 2 or 6", the PU operation mode and External operation mode can be changed to
the Network operation mode during a stop (during motor stop, start command OFF) by the PU/
NET operation switchover (X65) signal, the External/NET operation switchover (X66) signal. (When
Pr. 79 = "6", switchover is enabled during operation.)
● To switch between the Network operation mode and the PU operation mode
Set Pr. 79 = "0 (initial value) or 6".
Set Pr. 340 "Communication startup mode selection" = "10 or 12".
Set "65" in any of Pr. 178 to Pr. 189 to assign the NET-PU operation switching signal(X65) to a
terminal.
When the X65 signal is ON, the PU operation mode is selected. When the X65 signal is OFF, the
Network operation mode is selected.
FR-F800
X16 signal status and operation
mode
ON (External)
External
operation mode
1
PU operation mode
2
External operation mode
External/PU combined operation
3, 4
mode
External
6
operation mode
X12 (MRS)
External
ON
operation mode
X12 (MRS)
External operation mode
OFF
Operation mode switching by signal X16
(D) Operation command and frequency command
Remarks
OFF (PU)
PU operation
Switching among the External, PU, and NET operation modes
mode
is enabled.
PU operation mode fixed
External operation mode fixed. (Switching to NET operation
mode is enabled.)
External/PU combined operation mode fixed
PU operation
Switching among the External, PU, and NET operation mode
mode
is enabled while running.
PU operation
Switching among the External, PU, and NET operation mode
mode
is enabled. (In the External operation mode, output shutoff.)
External operation mode fixed. (Forcibly switched to External
operation mode.)
5 - 123