Main circuit terminals
● 400 V class (440 V input power supply )
Terminal
Applicable
screw
inverter model
FR-F840-
size
00023(0.75K) to
M4
00083(3.7K)
00126(5.5K)
M4
00170(7.5K)
M4
00250(11K)
M4
00310(15K)
M5
00380(18.5K)
M5
00470(22K)
M6
00620(30K)
M6
00770(37K)
M6
00930(45K)
M8
01160(55K)
M8
01800(75K)
M8
02160(90K)
M10
02600(110K)
M10
03250(132K)
M10(M12)
03610(160K)
M10(M12)
04320(185K)
M12(M10)
04810(220K)
M12(M10)
05470(250K)
M12(M10)
06100(280K)
M12(M10)
06830(315K)
M12(M10)
Tab. 2-12:
Cable size (400 V class), LD rating
2 - 34
Crimping
terminal
Tighten-
ing
torque
R/L1,
R/L1,
Nm
S/L2,
U, V, W
S/L2,
T/L3
1.5
2-4
2-4
1.5
2-4
2-4
1.5
5.5-4
5.5-4
1.5
5.5-4
5.5-4
2.5
8-5
8-5
2.5
14-5
8-5
4.4
14-6
14-6
4.4
22-6
22-6
4.4
22-6
22-6
7.8
38-8
38-8
7.8
60-8
60-8
7.8
60-8
60-8
14.7
60-10
60-10
14.7
80-10
80-10
14.7
100-10 100-10
14.7
150-10 150-10
24.5
150-12 150-12
24.5
100-12 100-12 2×100
46
100-12 100-12 2×100
46
150-12 150-12 2×125
46
150-12 150-12 2×150
HIV cables, etc. (mm²)
Earthing
(ground-
U, V, W P/+, P1
ing)
T/L3
cable
2
2
2
2
2
2
3.5
3.5
3.5
3.5
3.5
3.5
5.5
5.5
5.5
5.5
8
8
8
5.5
14
8
14
8
14
14
22
14
22
22
22
14
22
22
22
14
38
38
38
22
60
60
60
22
60
60
60
22
60
60
60
22
80
80
80
22
100
100
100
38
125
125
100
38
150
150
150
38
2×100
2×100
60
2×100
2×100
60
2×125
2×125
60
2×150
2×125
60
Installation and wiring
Cable gauge
AWG/MCM
PVC cables, etc. (mm²)
R/L1,
R/L1,
S/L2,
U, V, W
S/L2,
U, V, W
T/L3
T/L3
14
14
2.5
12
14
2.5
12
12
4
10
10
6
8
8
10
6
8
16
6
6
16
4
4
25
4
4
25
1
2
50
1/0
1/0
50
1/0
1/0
50
1/0
1/0
50
3/0
3/0
70
4/0
4/0
95
250
250
120
300
300
150
2×4/0
2×4/0
2×95
2×4/0
2×4/0
2×95
2×250
2×250
2×120
2×300
2×300
2×150
Earthing
(ground-
ing)
cable
2.5
2.5
2.5
4
4
4
6
10
10
10
10
16
16
16
25
16
25
16
50
25
50
25
50
25
50
25
70
35
95
50
120
70
150
95
2×95
95
2×95
95
2×120
120
2×150
150

Advertisement