Mitsubishi Electric FR-F820-04750 Instruction Manual page 430

Hide thumbs Also See for FR-F820-04750:
Table of Contents

Advertisement

(T) Multi-Function Input Terminal Parameters
Relationship between the analog input terminal function and the calibration parameter
● Calibration parameter according to the terminal 1 function
Pr. 868
setting
0
(initial
value)
4
9999
Tab. 5-119: Terminal 1 functional calibration parameter
Use Pr. 148 "Stall prevention level at 0 V input" and Pr.149 "Stall prevention level at 10 V input" to
adjust the bias and gain for stall prevention operation level under V/F control and Advanced
magnetic flux vector control.
● Calibration parameter according to the terminal 4 function
Pr. 858
setting
0
(initial
value)
4
9999
Tab. 5-120: Terminal 4 functional calibration parameter
Use Pr. 148 "Stall prevention level at 0 V input" and Pr.149 "Stall prevention level at 10 V input" to
adjust the bias and gain for stall prevention operation level under V/F control and Advanced
magnetic flux vector control.
Change the stall prevention operation level at maximum analog input
(C18 (Pr. 920), C40 (Pr. 933))
To only change the stall prevention operation level setting (gain) of the maximum analog input volt-
age (current), set to C18 (Pr. 920), C40 (Pr. 933).
5 - 268
Terminal function
Bias setting
C2 (Pr. 902) "Terminal 2 frequency setting
bias frequency"
C3 (Pr. 902) "Terminal 2 frequency setting
bias"
Frequency (speed)
setting auxiliary
C5 (Pr. 904) "Terminal 4 frequency setting
bias frequency"
C6 (Pr. 904) "Terminal 4 frequency setting
bias "
C16 (Pr. 919) "Terminal 1 bias command
Stall prevention
(torque)"
operation level
C17 (Pr. 919) "Terminal 1 bias (torque)"
No function
Terminal function
Bias setting
C5 (Pr. 904) "Terminal 4 frequency setting
Frequency (speed)
bias frequency"
command
C6 (Pr. 904) "Terminal 4 frequency setting
bias"
C38 (Pr. 932) "Terminal 4 bias command
Stall prevention
(torque)"
operation level
C39 (Pr. 932) "Terminal 4 bias (torque)"
No function
Calibration parameter
Gain setting
Pr. 125 "Terminal 2 frequency setting gain
frequency"
C4 (Pr. 903) "Terminal 2 frequency setting
gain"
Pr. 126 "Terminal 4 frequency setting gain
frequency"
C7 (Pr. 905) "Terminal 4 frequency setting
gain"
C18 (Pr. 920) "Terminal 1 gain command
(torque)"
C19 (Pr. 920) "Terminal 1 gain (torque)"
Calibration parameter
Gain setting
Pr. 126 "Terminal 4 frequency setting gain
frequency"
C7 (Pr. 905) "Terminal 4 frequency setting
gain"
C40 (Pr. 933) "Terminal 4 gain command
(torque)"
C41 (Pr. 933) "Terminal 4 gain (torque)"
Parameters