2. Installation

2.1 General Information

The CA62 Alarm control panel was designed and tested in compliance with electromagnetic compatibility standards.
The following recommendations need to be observed for the proper performance of the alarm station:
➢ Ensure the alarm system is properly earthed (grounded).
➢ Insulate the high and low voltage cables and use different input openings on the box.
➢ Avoid any loops of connecting wires within the very box and in their passage over or under the printed-
circuit boarding.
➢ Additional relays MUSt Not be placed in the CA62 Alarm control panel box as these may generate
electromagnetic interference when switched.
- Use only relays with good insulation between contacts and the winding.
- Relays, connected to outputs with an open commutator, must be designed to accommodate
a 12 V DC driving voltage and an impedance at the winding greater than 400Ω.
➢ The cable connecting the control panel and the keyboard is quadruple.
It is strongly recommended not to: use this cable to make other connections - connect to a telephone
line, Flash-lamps control signals, sirens or relays.
➢ Avoid channels or cable forms that contain high voltage cables when placing the connecting cables. This
is very important in cases where such cables are being used to power electric motors, fluorescent lamps or
triple-phase voltage. Where the above is not possible, use only shielded cables, where the shield is grounded
only in the alarm system box.
2.2 СА62 Installation Steps
We recommend during the installation of СА62 to follow the next installation steps:
➢ Carefully plan the security system - the type, number and location of detectors, the location of all peripheral
devices, communication modules and the control panel, the type and length of connection wires and cables,
etc.
➢ Mount all system elements - СА62 control panel, detectors, peripheral devices - keyboards and proximity
card readers, indoor or outdoor sirens. During the mounting follow the described in item 2.6 connection
diagrams and choose the type of zone balancing - with 1, 2 or 3 resistors.
Attention: The numeration of the keyboards sequence is important, you have to follow strictly the order 1 to 8.
The different keyboard models supported by CA62 and their connection to the control panel are described in
details in item 2.7.
➢ Power up the system as follow the steps in item 2.14. Check the normal system operation - there is
communication between the control panel and the keyboards, and the LED indication of the detectors in the
system is working.
➢ Program the default configuration type 0, 1, 2 or 3 - the most suitable for your alarm system installation.
Details for default configurations are described in SECTION SUPPLEMENTS of this manual.
➢ Program all other necessary parameters concerning your alarm system installation, as follow the order:
peripheral devices, zones, partitions, programmable outputs (PGM), communicator, dialer, user and manager
access codes and attributes.
➢ Test the efficiency of your system installation.
Installation and Programming Manual - СА62 Alarm Control Panel
5