SIMPO Addressable Fire Alarm Panel – Maintenance Menus

1. INTRODUCTION

1.1. General Description

SIMPO is an addressable fire panel with maximum coverage of 48 zones and connecting and up to 2 loops. The panel
supports communication protocol Teletek Electronics (SIMPO TTE Loop) and operation with SensoIRIS addressable
device series.
Every SIMPO TTE Loop provides up to 250 devices (detectors and modules, regardless of the type).
An arbitrary number of devices can be added to each zone thus ensuring the easy adaptation of the system to any type
of configuration.
To avoid or significantly diminish problems when mounting the system, it must be carefully planned prior to installation.
This includes: setting an address for every device and planning a name of maximum 40 digits (including the
spaces) for each address, thereby ensuring easy access to the device.
According to the acting standards for establishing fire systems and the plan of the building, the devices must
be grouped in zones.

1.2. General Specifications

The front panel consists of LCD module (4 rows x 40 symbols), functional buttons and system status LED indication.
Separate access level passwords provide access to the functions of the panel.
The fire alarm panel is designed on module structure as in the metal cabinet there are provided additional places for
mounting of a second loop controller for Loop 2 (Loop 1 is built-in the main PCB), a communication module and
redundant network module.
The panel has a built-in real time clock and calendar, allowing day and night time modes of work.
Switching over between the two modes can be automatic or manual. Events like FIRE, RESET, FAULT, etc., are saved
in the memory, thereby creating an event log-file. It contains the time and date, the address of the device, the name of
the device, the zone number, the name of the zone, etc.