I/O device analog input/analog output
10.2 I/O device analog output
Technical specifications
•
Between 1L+, channels and all other circuit ele
ments
•
Between channels
•
Between Ethernet and all other circuit elements Yes
See also
Response times for analog input device and output device (Page 259)
10.2.2
Parameter overview analog output
Parameters for analog output 4 AO U/I 4xM12 (6ES7145-6HD00-0AB0)
Parameters
Group diagnostics
Diagnostics, missing 1L+
Diagnostics, sensor supply
short-circuit
Response to CPU/Master
STOP
Type of output
Output range
Diagnostics, wire break at
outputs
Diagnostics, short-circuit at
outputs
Diagnostics, overload
Substitute value
194
No
No
Range of values
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
•
Output has no current or
voltage
•
Retain last value
•
Switch to substitute val
ues
•
Disabled
•
Voltage
•
Current
•
1 to 5 V
•
0 to 10 V
•
±10 V
•
0 to 20 mA
•
4 to 20 mA
•
±20 mA
•
Disable
•
Enable
•
Disable
•
Enable
•
Disable
•
Enable
Each value in the nominal
range, overrange, and
underrange
Default setting
Range of effective
ness
Disable
Device
Disable
Device
Disable
Device
Output has no current
Device
or voltage
Voltage
Channel
±10 V
Channel
Disable
Channel
Disable
Channel
Disable
Channel
0
Channel
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN