Parameters for analog input 8 AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)
Parameters
Group diagnostics
Diagnostics, missing 1L+
Interference frequency suppres
sion
Temperature unit
Reference temperature for TC
Measurement type, channels 0
to 7
Measuring range, channels 0 to
7
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Range of values
•
Disable
•
Enable
•
Disable
•
Enable
•
Off (Fast Mode)
•
60 Hz
•
50 Hz
•
10 Hz
•
Celsius
•
Fahrenheit
•
Kelvin
•
-145.0 to 155.0 (Celsius)
•
-229.0 to 311.0 (Fahrenheit)
•
128.2 to 428.2 (Kelvin)
•
Disabled
•
Voltage +/-80 mV
•
Resistance (4-wire connection)
•
Resistance (3-wire connection)
•
Resistance (2-wire connection)
•
Thermoresistor
(linear, 4-conductor connection)
•
Thermoresistor
(linear, 3-conductor connection)
•
Thermoresistor
(linear, 2-conductor connection)
•
Thermocouple elements
•
+/-80 mV
•
150 Ω
•
300 Ω
•
600 Ω
•
3000 Ω
•
Pt100 Climatic range
•
Pt100 Standard range
•
Pt200 Climatic range
•
Pt200 Standard range
•
Pt500 Climatic range
•
Pt500 Standard range
•
Pt1000 Climatic range
•
Pt1000 Standard range
•
Ni100 Climatic range
•
Ni100 Standard range
•
Ni120 Climatic range
•
Ni120 Standard range
•
Ni200 Climatic range
•
Ni200 Standard range
•
Ni500 Climatic range
•
Ni500 Standard range
•
Ni1000 Climatic range
I/O device analog input/analog output
10.1 I/O device analog input
Default setting
Range of effectiveness
Disable
Device
Disable
Device
50 Hz
Device
Celsius
Device
0.0
Device
Thermoresistor Pt100
Channel
(4-conductor connec
tion)
Pt100 Standard range
Channel
169