Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual page 168

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

Parameters for analog input 8 AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0)
Parameters
Group diagnostics
Diagnostics, missing 1L+
Interference frequency suppres­
sion
Temperature unit
Reference temperature for TC
Measurement type, channels 0
to 7
Measuring range, channels 0 to
7
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Range of values
Disable
Enable
Disable
Enable
Off (Fast Mode)
60 Hz
50 Hz
10 Hz
Celsius
Fahrenheit
Kelvin
-145.0 to 155.0 (Celsius)
-229.0 to 311.0 (Fahrenheit)
128.2 to 428.2 (Kelvin)
Disabled
Voltage +/-80 mV
Resistance (4-wire connection)
Resistance (3-wire connection)
Resistance (2-wire connection)
Thermoresistor
(linear, 4-conductor connection)
Thermoresistor
(linear, 3-conductor connection)
Thermoresistor
(linear, 2-conductor connection)
Thermocouple elements
+/-80 mV
150 Ω
300 Ω
600 Ω
3000 Ω
Pt100 Climatic range
Pt100 Standard range
Pt200 Climatic range
Pt200 Standard range
Pt500 Climatic range
Pt500 Standard range
Pt1000 Climatic range
Pt1000 Standard range
Ni100 Climatic range
Ni100 Standard range
Ni120 Climatic range
Ni120 Standard range
Ni200 Climatic range
Ni200 Standard range
Ni500 Climatic range
Ni500 Standard range
Ni1000 Climatic range
I/O device analog input/analog output
10.1 I/O device analog input
Default setting
Range of effectiveness
Disable
Device
Disable
Device
50 Hz
Device
Celsius
Device
0.0
Device
Thermoresistor Pt100
Channel
(4-conductor connec­
tion)
Pt100 Standard range
Channel
169

Advertisement

Table of Contents
loading

Table of Contents