7.5.4

STOP of the IO Controller and recovery of the IO Device

Diagnostics events triggered after a STOP of the IO Controller
Diagnostics frames received from the IO Device while the IO Controller is in STOP do not
trigger the start of corresponding OBs after the restart of the IO Controller. You must
explicitly read the diagnostics data from OB 100 to obtain an overview of the device state.
Diagnostics after recovery of the IO Device
You must explicitly read data record E00C
This record contains all diagnostics data for the device slots assigned to an IO Controller
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Error text
Invalid cycle time
Revision error
Implausible device
Interrupt, error, and system messages
Meaning
Check cycle time
Incomplete protocol version
by calling SFB 52 after recovery of an IO Device.