Pin Assignment For Parameterizable Digital Input/Digital Output - Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

When using the Y cable, pin 2 and pin 4 are assigned to pin 4 (B) and pin 4 (A).
NOTE
The M12 sockets for the supply and I/O have the same coding.
Make sure that you wire the supply and the I/O correctly.
3.6.5

Pin assignment for parameterizable digital input/digital output

I/O device 8 DIO DC 24V/1,3A 8×M12 (6ES7147-6BG00-0AB0)
You will find the pin assignment for the 8 DIO DC 24V/1,3A 8×M12 I/O device in the table
below.
Table 3-11  Pin assignment of the M12 cable connector for the 8 DIO DC 24V/1,3A 8×M12 I/O device
Pin
1*
2
3
4
5
1
2
3
4
5
* The sensor supply is only available when the corresponding channel is parameterized as an "Input".
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Assignment
Assignment X1 to X4 (1L+ non-switched)
24 V sensor supply 1U
S
(derived from 1L+ non-switched)
Not used
Supply ground 1M
Input / output signal DIQ
: Connector X1
0
Input/output signal DIQ
: Connector X2
1
Input/output signal DIQ
: Connector X3
2
Input/output signal DIQ
: Connector X4
3
Functional earth FE
Assignment X5 to X8 (2L+ switched)
24 V sensor supply 2U
S
(derived from 2L+ switched)
Not used
Supply ground 2M
Input / output signal DIQ
: Connector X5
4
Input/output signal DIQ
: Connector X6
5
Input/output signal DIQ
: Connector X7
6
Input/output signal DIQ
: Connector X8
7
Functional earth FE
3.6 Pin assignment of connectors
View of the cable connector (wiring
side)
Input
Output
Wiring
47

Advertisement

Table of Contents
loading