IO-Link Master
11.2 IO-Link Master (6ES7148-6JD00-0AB0)
Technical specifications
•
between 1L+ and 2L+
•
between 1L+, channels and all other switching
parts
•
Between channels
•
between Ethernet and all other switching parts Yes
Status, interrupts, diagnostics
Interrupts
•
Hardware interrupt (device notification)
Diagnostics function
•
Group error/maintenance
•
Bus monitoring PROFINET IO
•
Monitoring of supply voltage 1L+
•
Monitoring of supply voltage 2L+
•
Existing connection to network
•
IO-Link port
– Port in IO-Link mode
– Port in SIO mode
•
Diagnostic information can be read
Monitoring for
•
Missing 2L+
•
Sensor supply short-circuit
Sensor supply
Number of outputs
Load current
Short-circuit protection
IO-Link port
Number of ports
Number of ports that can be controlled simultan
eously
IO-Link protocol 1.0
IO-Link protocol 1.1
Transmission rate
Size of the process data, input per port
Size of the process data, input per module
Size of the process data, output per port
Size of the process data, output per module
Memory size for device parameters
Master backup
212
Yes
No
No
Yes
Yes
Yes
Yes; red/yellow LED "SF/MT"
Red "BF" LED
Green "ON" LED
Green "24 V DC" LED
Green "P1 LK" and "P2 LK" LED for PROFINET IO
infeed and loop-through
green/red LED "IO-L"
Green LED "Q"
Yes
Yes
Yes; device supply to ground
4
500 mA per output
Yes, electronic
4
4, in all mounting positions
Yes
Yes
4.8 kBaud (COM1), 38.4 kBaud (COM2), 230.4
kBaud (COM3)
32 bytes + 1 byte PQI
128 bytes + 4 bytes PQI
32 bytes
128 bytes
2 Kbytes; for each port
possible; with function block LIOLink_Master
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN