Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual page 99

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

General technical data
8.3 Mechanical and climatic environmental conditions
Designation
8 AI RTD/TC 8×M12
4 AO U/I 4×M12
4 IO-L + 8 DI + 4 DO DC 24V/1,3A 8×M12
4 IO-L 4×M12
PD DC 24V 1×7/8" 4×M12
Terminal block
Mounting rail
Mechanical environmental conditions
The table below shows the mechanical environmental conditions in the form of sinusoidal
oscillation.
Devices
Frequency band
Without mounting rail
10 ≤ f ≤ 58 Hz
58 ≤ f ≤ 150 Hz
With mounting rail
5 ≤ f ≤ 8 Hz
8 ≤ f ≤ 150 Hz
Compatibility test, mechanical environmental conditions
The table below provides information about the type and scope of the tests of mechanical
environmental conditions.
Test ...
Test standard
Vibration
Vibration test accord­
ing to IEC 60068-2-6
100
Article number
6ES7144-6KD50-0AB0
6ES7145-6HD00-0AB0
6ES7148-6JA00-0AB0
6ES7148-6JD00-0AB0
6ES7148-6CB00-0AA0
6ES7194-6CA00-0AA0
6ES7194-6GA00-0AA0
Continuous
1.5 mm amplitude
20 g constant acceleration
15 mm amplitude
5 g constant acceleration
Terminal and I/O devices
Type of vibration: Frequency sweeps at a rate of change of 1
octave/minute.
Without
10 Hz ≤ f ≤ 58 Hz, constant amplitude 3 mm
mounting rail
58 Hz ≤ f ≤ 150 Hz, constant acceleration 40 g
With mounting
5 Hz ≤ f ≤ 12 Hz, constant amplitude 15 mm
rail
12 Hz ≤ f ≤ 150 Hz, constant acceleration 10 g
Duration of vibration: 10 frequency sweeps per axis in each of
three perpendicular axes
Fields of application
-25 °C to
-25 °C to
-40 °C to
55 °C
60 °C
60 °C
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Tested at ...
3 mm amplitude
40 g constant acceleration
-
10 g constant acceleration
Operating Instructions, 06/2022, A5E01250250-AN
From product
version
X
1
1
X
4
1
X
1
1
1
X