Emc Compatibility, Shipping And Storage Conditions - Siemens SIMATIC Distributed I/O ET 200eco PN Operating Instructions Manual

Hide thumbs Also See for SIMATIC Distributed I/O ET 200eco PN:
Table of Contents

Advertisement

Marine approval
Classification authorities:
• ABS (American Bureau of Shipping)
• BV (Bureau Veritas)
• CCS (China Classification Society)
• DNVGL (Det Norske Veritas / Germanischer LIoyd)
• KR (Korean Register of Shipping)
• LRS (Lloyds Register of Shipping)
• Class NK (Nippon Kaiji Kyokai)
The article numbers of the approved I/O devices for the respective classification society can
be found here (https://support.industry.siemens.com/cs/ww/en/ps/14244/cert?ct=446).
See also
PI explosion protection use ecoPN
(https://support.industry.siemens.com/cs/ww/en/view/80484830)
8.2

EMC compatibility, shipping and storage conditions

Definition
Electromagnetic compatibility is the ability of an electrical device to function in its
electromagnetic environment in a satisfactory manner without affecting this environment.
The ET 200eco PN distributed I/O device also meets the requirements of the EMC law of the
European Single Market. Prerequisite is compliance of the electrical configuration of the
ET 200eco PN distributed I/O device with specifications and directives.
Pulse-shaped disturbances
The table below shows the electromagnetic compatibility of the ET 200eco PN distributed I/O
device with respect to pulse-shaped disturbances.
Pulse-shaped disturbance
Electrostatic discharge to
IEC 61000-4-2
Burst pulses (high-speed transient
disturbances) according to
IEC 61000-4-4.
High-energy single pulse (surge) according to IEC 61000-4-5 *
Asymmetric coupling
Symmetric coupling
* On DC 24 V supply only with protective element
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
8.2 EMC compatibility, shipping and storage conditions
Test voltage
8 kV
6 kV
2 kV (power supply line)
2 kV (signal line)
2 kV (power supply line)
2 kV (signal / data line)
1 kV (power supply line)
1 kV (signal / data line)
General technical data
corresponds with degree of
severity
3 (air discharge)
3 (contact discharge)
3
4
3
97

Advertisement

Table of Contents