Technical Data; Analog Output Module - Siemens SENTRON VL Series System Manual

Circuit breakers with communication capability - profibus
Hide thumbs Also See for SENTRON VL Series:
Table of Contents

Advertisement

3WL air circuit breakers
3.5 External CubicleBUS modules
3.5.4.2

Technical data

The table below shows the technical data of the digital configurable output module on the
CubicleBUS:
Table 3- 19
Operating voltage on the CubicleBUS min./max. (V)
Current consumption from the CubicleBUS min./max. (mA)
Number of isolated channels per digital output module
Max. possible current per channel with 24 V DC relay
Max. aggregate current (6 channels) relay at
24 V DC/250 V AC/250 V DC (A)
Maximum number of modules on one Cubicle
Power loss min./typ./max. (W)
Dimensions W/H/D (mm)
Weight (kg)/relay
Temperature range (°C)
3.5.5

Analog output module

Via the analog output module, the most important measured values made available via the
CubicleBUS can be output to analog indicator instruments, e.g. rotary coil instruments, in the
control cabinet door. Four channels are available in each analog output module for this
purpose. The signals are available at two physical interfaces, a 4 - 20 mA interface and a 0 -
10 V interface.
76
Technical data of the digital configurable output module
3WL/3VL circuit breakers with communication capability - PROFIBUS
System Manual, 03/2011, A5E01051353-02
19.2 / 28.8
29/39 (250 rel.)
6
2.7
10 / 10 / 2.5
1
0.74 / 5.4
70 / 86 / 95
0.321
– 20 / 60