I/O device analog input/analog output
10.2 I/O device analog output
Technical specifications
Number of actuator supplies
Total current
Short-circuit protection
Response threshold
Actuator selection data
Output ranges (Rated value)
Voltage
Current
Load resistance (in the Rated range of the output)
For voltage outputs
For voltage outputs, capacitive load
For current outputs
For current outputs, inductive load
Permissible input voltage at the output (destruction
limit)
Connection of actuators
For voltage output, 2-wire connection
For current output, 2-wire connection
Formation of analog values
Conversion principle
Conversion time per channel, in ms
Voltage resolution (including overrange)
Current resolution (including overrange)
Settling time
For resistive load
For capacitive load
For inductive load
Ability to switch to substitute values
Interference suppression, error limits
Crosstalk between outputs
192
4
Max. 1 A
Yes, electronic
Min. 1.4 A
±10 V
1 V to 5 V
0 V to 10 V
±20 mA
4 to 20 mA
0 to 20 mA
Min. 1 kΩ
Max. 1 μF
Max. 0.6 kΩ
Max. 1 mH
28.8 V continuous, 35 V for 500 ms
Yes
Yes
Resistor network
1 ms
±10 V/15 bits + sign
1 to 5 V/15 bits
0 to 10 V/15 bits
±20 mA/15 bits + sign
4 to 20 mA/15 bits
0 to 20 mA/15 bits
U
I
1.3 ms
2 ms
1.8 ms
-
-
2 ms
Yes
Min. 70 dB
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN