Sign
The sign (S) of the analog value is always in bit number 15:
• "0" → +
• "1" → -
10.1.6

Measuring ranges of the analog input device in S7 format

Voltage measuring ranges: Measuring range 1 to 5 V
Measuring range
1 to 5 V
> 5.704 V
5.704 V
5 V
4 V
1 V + 144.7 µV
1 V
0.296 V
< 0.296 V
Voltage measuring ranges: Measuring range 0 to 10 V
Measuring range
0 to 10 V
> 11.759 V
11.759 V
10 V
7.5 V
0 V + 361.7 µV
0 V
-1.759 V
< -1.759 V
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
Units
Decimal
32767
32511
27649
27648
20736
1
0
-1
-4864
32767
- 32768
Units
Decimal
32767
32511
27649
27648
20736
1
0
-1
-4864
- 32768
I/O device analog input/analog output
10.1 I/O device analog input
Hexadecimal
7FFF
Overflow
H
7EFF
Overrange
H
6C01
H
6C00
Nominal range
H
5100
H
0001
H
0000
H
FFFF
Underrange
H
ED00
H
7FFF
Wire break
H
8000
Underflow
H
Hexadecimal
7FFF
Overflow
H
7EFF
Overrange
H
6C01
H
6C00
Nominal range
H
5100
H
0001
H
0000
H
FFFF
Underrange
H
ED00
H
8000
Underflow
H
Range