IO-Link Master
11.1 IO-Link Master (6ES7148-6JA00-0AB0)
Technical data
•
Between Ethernet and all other circuit elements Yes
Status, interrupts, diagnostics
Interrupts
Diagnostics function
•
Group error/maintenance
•
Bus monitoring PROFINET IO
•
Monitoring of supply voltage 1L+
•
Monitoring of supply voltage 2L+
•
Existing connection to network
•
IO-Link port
•
Digital input/digital output
•
Fault at digital input/digital output
•
Diagnostic information can be read
Monitoring for
•
Missing 2L+
•
Short-circuit of the sensor supply to M
•
Short-circuit at output (Channel 0 to 3)
•
Wire break at input
•
Wire break at output (Channel 0 to 3)
Sensor supply
Number of sensor supplies
Load current
Short-circuit protection
IO-Link port
Number of ports
Number of ports that can be controlled simultan
eously
IO-Link protocol 1.0
IO-Link protocol 1.1
Transmission rate
Size of the process data, input per port
Size of the process data, input per module
Size of the process data, output per port
Size of the process data, output per module
Digital inputs
Number of inputs
204
Yes
Yes
Red LED / yellow LED "SF/MT"
Red "BF" LED
Green "ON" LED
Green "24 V DC" LED
Green "P1 LK" and "P2 LK" LED; LED for PROFINET IO
infeed and loop-through
Green LED "IO-L"
Green LED
Red LED
Yes
Yes
Yes, for Channels 4 to 7, per channel group
Yes, per channel
Input current < 0.3 mA per channel
Yes, in the off state, per channel
6 (X1-X4 (IO-LINK/DI) and X5-X6 (DI))
200 mA per output to X1-X4 (IO-LINK/DI)
100 mA per output to X5-X6 (DI)
Yes, electronic
4
4, in all mounting positions
Yes
No
4.8 kBaud (COM1), 38.4 kBaud (COM2)
32 bytes
32 bytes
32 bytes
32 bytes
8
Operating Instructions, 06/2022, A5E01250250-AN
ET 200eco PN