4. Use the following cables with even connector outlets to wire the different M12 interfaces:
– PROFINET: SIEMENS, order number 6XV1 870-8A or 6XV1 871-5T
– Supply voltage: SIEMENS, order number 6XV1 801-5D
– Encoders and actuators: SIEMENS, Y-cable, order number 6ES7194-6KA00-0XA0;
5. All M12 connectors must be protected against unauthorized opening, for example with
safety clips. Suitable safety clips are available with PHOENIX CONTACT *, product
designation SAC-M12-EXCLIP-F or SAC-M12-EXCLIP-M.
6. All unoccupied M12 circular sockets should be closed using sealing caps in such a way that
the caps cannot be loosened by hand (torque: 0.6 Nm). Suitable sealing caps are available
from: Binder GmbH + Co. **, item no. 08 2769 000 000.
* PHOENIX CONTACT GmbH & Co. KG, Flachsmarktstr. 8, D-32825 D-Blomberg,
http://www.phoenixcontact.com (http://www.phoenixcontact.com)
** Fa. Binder GmbH & Co., Elektrische Bauelemente KG, Rötelstr. 7, D-74148 Neckarlsulm,
http://www.binder-connector.com (http://www.binder-connector.com)
ET 200eco PN
Operating Instructions, 06/2022, A5E01250250-AN
PHOENIX CONTACT *, product designation SAC-3P-M12MS
8.6 Use of the ET 200eco PN in zone 2/zone 22 hazardous areas
General technical data