Setting Mode
lset.h
lset.l
FUNCTION
SETTING
REFERENCE
MODELS
Upper Limit (H) of Linear Output Range
Lower Limit (L) of Linear Output Range
Linear output setting is made in the option menu to enable the K3NR to have
voltage or current output in proportion to the change in display value.
• The maximum and minimum values of linear output are set in this parameter.
Linear output
20 mA or 5 V
4 mA or 1 V
• L can be greater or less than H.
• L cannot be the same as H, otherwise H will be automatically set to a value
obtained by adding 1 to L.
• The teaching function can be used for setting linear output ranges.
Setting range
–19999 to 99999
Refer to 6-1 Teaching Function.
This setting is available for the K3NR with the Linear Output Board.
H linear output range
L linear output range
Section 4-2
Display value
Default
99999
–19999
83