Chapter 6 Control Modes of Operation|ASDA-B Series
6.2.3 Pulse Inhibit Input Function (INHP)
INHP is activated via digital inputs (Please refer to parameter P2-10 ~ P2-15 and DI INHP(07) in Table
7.A).When the drive is in position mode, if INHP is activated, the external pulse input command is not
valid and the motor will stop.
6.2.4 Electronic Gear Ratio
Relevant parameters:
P1 - 15▲
GR4
Electronic Gear Ratio (2nd Numerator) (N2)
Default: 1
Applicable Control Mode: P
Unit: pulse
Range: 1 ~ 32767
Settings:
The electronic gear numerator value can be set via external DI signal (refer to Table 7.A).
DI Name
GNUM0
NOTE
1) DI signal can be selected by parameter P2-10 to P2-15 and Table 7.A. If uses only need to
use one group of electronic gear, it allows users not to select GNUM0.
P1 - 44▲
GR1
Electronic Gear Ratio (1st Numerator) (N1)
Default: 1
Applicable Control Mode: P
Unit: pulse
Range: 1 ~ 32767
Settings:
The electronic gear numerator value can be set via external DI signal (refer to Table 7.A).
6-4
INHP
ON
Pulse
command
DI Status
Not select (Note 1)
OFF
Selected Electronic Gear
P1-44, P1-45
0
P1-44, P1-45
1
P1-44, P1-45
ON
Communication Addr.: 010FH
Related Section:
Section 6.2.4, P1-44, P1-45
DI GNUM0(11) in Table 7.A
Communication Addr.: 012CH
Related Section:
Section 6.2.4, P1-15, P1-45
DI GNUM0(11) in Table 7.A