High Level Network Settings - HMS Networks Anybus Communicator ABC3028 User Manual

Modbus tcp to modbus rtu/serial
Table of Contents

Advertisement

Communicator Configuration
7.9

High Level Network Settings

Configure the Modbus TCP network settings.
7.9.1
To Use Automatic I/O Sizes
By default, the Communicator is set to use automatic I/O sizes.
The size of the input data, Data Size to Modbus TCP, and the output data, Data Size from
Modbus TCP, is determined by the subnetwork configuration.
In the Communicator built-in web interface, the Use Automatic I/O Sizes checkbox is selected.
7.9.2
To Configure I/O Sizes Manually
1.
Deselect the Use Automatic I/O Sizes checkbox.
2.
Enter a value for Data Size to Modbus TCP and a value for Data Size from Modbus TCP.
®
Anybus
Communicator
User Manual
67 (124)
SCM-1202-162 1.1 en-US