Required Conduits; Layout - Gasboy Islander Prime Instruction And Installation Manual

Table of Contents

Advertisement

Preliminary Guidelines

4.4.3 Required Conduits

The types of conduits in the island are a function of the different equipment and location in the
island. There are two functional conduits:
• High voltage conduits
• Low voltage conduits
The following conduits are required in the Island:
• High voltage conduits
• Low voltage conduits
• Grounding
• Tank conduit

4.4.4 Layout

Four conduits can be inserted in Islander Prime, each carrying specific wires (see
Table 3:
No.
1
2
3
Page 28
- AC power for Islander Prime
- Pump control from mechanical pumps to Islander Prime
- Pump In-use signal from mechanical pumps to Islander Prime
- Internet line from LAN at Office to Islander Prime
- RS-232 communication line from TLG at office to Islander Prime
- RS-485/422/C.L. or Tokheim
- Pulser from pumps to Islander Prime
- At least 10 mm (OOO AWG) Grounding cable to pump chassis
- At least 10 mm (OOO AWG) Grounding cable to Islander Prime pole (Connected to the
external chassis grounding post)
- Grounding cable to TLG – in accordance with TLG manufacturer instructions
- TLG Probe
Conduits into Islander Prime
Conduit Type
Type
Low voltage
Pulser, TLG, LAN
High voltage
AC power, GND, In-use
High voltage
Control
MDE-5411A ForeHB Islander Prime Installation Manual · October 2018
4.4 Conduits
Table
3).