Mechanical Pump Does Not Fuel - Gasboy Islander Prime Instruction And Installation Manual

Table of Contents

Advertisement

Troubleshooting

8.2.2 Mechanical Pump Does Not Fuel

The following table describes the Islander Prime troubleshooting procedure and appropriate
corrective actions when the mechanical pump does not fuel (see
Table 24: Mechanical Pump Does Not Fuel
Fault
Pump does not supply
fuel.
Pump is authorized
but call state is not
detected (nozzle icon
in SiteOmat Status
screen does not
display call state).
Pump is authorized,
pump motor is running,
but no fuel is supplied.
Page 86
Probable
Cause
Checks
Pump setup is
Check pump setup:
incorrect
• Pump server Buses
• Prices Pulse Rate
Faulty connection
Check Control cables
to pump
from Islander Prime to
pump.
LAN to 3x 485
Verify that Power LED
CommVerter
is lit.
Verify that the Control
red LED on MPI-C
board is lit.
Pump malfunction Turn the Islander Prime
bypass switch on; lift
the nozzle, and check
that the pump supplies
fuel.
Handle-on switch
Is the In Use red LED
problem
MPI-C board lit when
nozzle is lifted?
Faulty in-use
Power off the pump;
switch in pump
then, using an
ohmmeter,
measure the switch
in on and off states.
Faulty
• Check In Use
connections
cable.
• Check In Use
terminal block
connections.
Faulty In Use
terminal block
Faulty MPI-C
Verify that the Call red
board
LED is lit when nozzle
is lifted.
Faulty LAN to 3x
485 CommVerter
• Faulty
Does the pump
solenoid valve
solenoid valve produce
• Faulty pump
a clicking sound?
MDE-5411A ForeHB Islander Prime Installation Manual · October 2018
8.2 Islander Prime
Table
24):
Corrective Action
1
Set pump parameters.
2
Save and reload.
3
Check again.
Make a secure electrical connection.
If it is off, use a voltmeter to check power
supply to the unit: If power supply is OK,
then replace the LAN to 3x 485
CommVerter board. If power supply is
faulty, replace the power supply.
1
Replace MPI-C board.
1
Replace LAN to 3x 485 CommVerter.
If the problem persists:
1
Check Handle-on switch.
2
Repair pump.
1
Check In Use cable and repair (if
necessary).
2
Check terminal wires and repair (if
necessary).
3
Check In Use switch in the pump and
repair (if necessary).
Replace pump switch in cases
where no short was detected.
Make good electrical connection if faulty
one exists.
Replace In-use terminal block.
• If the red LED is not lit, replace the
MPI-C board.
• If the LED is lit, the problem is
external to the controller.
Replace the LAN to 3x 485 CommVerter.
• Replace valve
• Repair pump