Transient Editing - Pacific UPC-32 Operation Manual

Table of Contents

Advertisement

4.5.2 TRANSIENT EDITING

Before beginning to create a transient, the sequence of the voltage, frequency, and waveform changes
should be fully defined. The UPC allows transient events to be defined in two ways: Time-based
transients and Cycle-based transients.
Transient event timing always begins at 0 degrees of ΦA (the rising 0 volt crossing), and will proceed
based on defined Segments. Each Segment has 5 editable values:
a) SEGMENT #
b) Time
c) Voltage(s)
d) Frequency
e) Waveform(s)
Time-based transients use absolute time to sequence through the defined segments. Each segment has
a duration, defined by T= <0.0002 to 300 secs>. Up to 99 segments can be defined in a transient event.
The total transient duration will be the sum of the defined segment times.
Cycle-based transient segments substitute a single cycle of a specified waveform. Up to 99 segments
can be defined in a transient event. Each segment may use any waveform. The transient duration is
counted in number of cycles and is therefore dependent on frequency. Custom waveforms can be
created (see 4.6.2) or the existing waveform table (see 2.1.4) may be used.
Transient sequences can be repeated, from single events to endless looping, terminated by the operator.
There is a limit of 1000 transient segment storage in the UPC. It is not possible to have 99 Programs
with each having a 99 segment transient.
Transient voltage amplitudes will be calculated based on the RMS voltage or on the amplitude of the
Program that contains the transient. The calculation method is defined by the TRANSIENT WFs setting
in the GENERAL SETUP tables (see 4.6.3.9).
RMS=ENABLED, causes all transient voltages to be calculated as true RMS.
RMS=DISABLED, causes the transient voltages to be referenced to the Program voltage
To start the Transient Edit Mode from any meter display, press the PROGRAM key, select a program
number, press the ENTER key then EDIT key. The cursor will move to FORM. This example uses the
program #4 information as described in the previous example.
PROGRAM: #4
FREQ=400
#SEGS=0
From the PROGRAM edit display, pressing EDIT again allows transients to be created and edited. The
TRANSIENT edit display will become active.
TRANSIENT: PRGM #4
T=0.0002
F=400
defines the order of segment execution
defines the duration of the segment
defines the Voltage at the end of the segment
defines the frequency at the end of the segment
defines the waveform used for the duration of the segment
and waveform for that phase.
FORM=3 COUPLING=DIRECT
Va=108
Vb=108
WFa=1
WFb=1
Ilim=50
PHb=120º
SEGMENT #1
Va=108
Vb=108
WFa=1
WFb=1
51
SECTION 4
Vc=108
WFc=1
PHc=240º
OF 1
Vc=108
WFc=1
OPERATION

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Pacific UPC-32

This manual is also suitable for:

Upc-12

Table of Contents