5.5.2 METERED DATA QUERIES (cont)
:MEASure:PF1?
:MEASure:PF2?
:MEASure:PF3?
:FETCh[:WAVEform]:VOLT1?
:FETCh[:WAVEform]:CURRent1? Query: metered waveform data (line-to-neutral voltage only).
:MEASure:SPECTrum:VOLT1[:MAGnitude]
:MEASure:SPECTrum:CURRent1[:MAGnitude]
:MEASure:SPECTrum:PHASe
:MEASure:SPECTrum:THD?
:MEASure:SPECTrum:OHD?
:MEASure:SPECTrum:EHD?
Query: metered power factor (KW/KVA) ΦA.
Returns <0> to <1.0>
Query: metered power factor (KW/KVA) ΦB.
Returns <0> to <1.0>
Query: metered power factor (KW/KVA) ΦC.
Returns <0> to <1.0>
Use :VOLT1 for ΦA, :VOLT2 for ΦB, and :VOLT3 for ΦC volts
Use :CURR1 for ΦA, :CURR2 for ΦB, and :CURR3 for ΦC current
Returns a string of 512, NR2 type numbers, comma delimited. Each
waveform string is terminated by a semi-colon.
Query: waveform harmonic magnitudes
Use :VOLT1 for ΦA, :VOLT2 for ΦB, and :VOLT3 for ΦC volts
Use :CURR1 for ΦA, :CURR2 for ΦB, and :CURR3 for ΦC current
Returns a data set of up to 256 (default=64), NR2 type numbers,
comma delimited, representing harmonic magnitudes.
element is the magnitude of the fundamental, for reference. The 2nd
element is the 2nd harmonic, etc. Each magnitude is a percent of the
fundamental.
The
:SENSe:SPECTrum:RANGe. See para. 4.3.1.1 and 5.4.2.
(option: Harmonic Analysis and Synthesis)
Query: phase angles in degrees for the most recent harmonics data
Returns a data set of up to 256, NR2 type numbers, comma delimited.
The first element is the angle of the fundamental, for reference. The
2nd element is the angle of the 2nd harmonic, etc. The previous
:MEASure:SPECTrum:parameter command defines which phase
angles are sent. If parameter was VOLT1 then the phase angles will
be for VOLT1.
(option: Harmonic Analysis and Synthesis)
Query: Returns Total Harmonic Distortion of the most recent
:MEASure:SPECTrum:parameter command, as above.
(option: Harmonic Analysis and Synthesis)
Query: Returns Odd Harmonic Distortion of the most recent
:MEASure:SPECTrum:parameter command, as above.
(option: Harmonic Analysis and Synthesis)
Query: Returns Even Harmonic Distortion of the most recent
:MEASure:SPECTrum:parameter command, as above.
89
SECTION 5
REMOTE OPERATION
(option: Harmonic Analysis and Synthesis)
number
of
harmonics
The first
is
defined
by