User Diagnostics - Pacific UPC-32 Operation Manual

Table of Contents

Advertisement

9

USER DIAGNOSTICS

This section is intended to aid the user in solving common problems that may occur while using the
UPC.
PROBLEM
Incorrect or illogical operation,
or program values invalid,
or "NO PROGRAM RUNNING",
or "FPERR" is displayed.
PROBLEM
LCD Display not readable
SECTION 9
USER DIAGNOSTICS
PROBABLE CAUSE –
Battery backed RAM information corrupt.
SUGGESTED CURE:
Clear ALL RAM and RESET CPU.
Refer to section 4.6.1.3 to perform this function.
To prevent the UPC from executing program parameters
upon power-up, hold the fn key down while applying power
with the INPUT POWER switch. You may then press fn
again to enter the SETUP mode.
If the problem recurs after power-down, the battery which
maintains the RAM data may need to be replaced
PROBABLE CAUSE –
Battery backed RAM information corrupt.
SUGGESTED CURE:
Clear ALL RAM and RESET CPU.
Refer to section 4.6.1.3 to perform this function, or hold
down the CLEAR key while applying INPUT POWER to the
UPC. This will clear ALL RAM and RESET the CPU.
115
SECTION 9
DIAGNOSTICS

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Pacific UPC-32

This manual is also suitable for:

Upc-12

Table of Contents