Example Of Program Query - Pacific UPC-32 Operation Manual

Table of Contents

Advertisement

5.7.2 EXAMPLE OF PROGRAM QUERY

:PROGram:NAME 1 <eos>
:PROGram:DEFine? <eos>
STEADY-STATE OUTPUT PARAMETERS returned
NOTE 1: To select a transient segment for query, send :PROGram:DEFine SEG,n <eos>, where n is
the segment of interest, then send the query, :PROGram:DEFine? <eos>, then address the UPC as a
talker. The steady-state values of the selected program and segment values of the most recently
selected segment will be returned by the UPC.
OPTIONAL TRANSIENT PARAMETERS returned
Step A. Address the UPC as a listener.
Step B. Select Program 1.
NOTE: <eos> is a LINE FEED (0Ahex, 10dec).
Step C. Query Program 1.
Program 1 consists of steady-state and optional transient segment
parameter names and values. This Query returns steady-state values
of the selected program and segment values of the most recently
selected segment (see NOTE 1). "LAST" is returned with segment
data if the segment is the last segment in the program.
Step D. Address the UPC as talker, read back the response string.
NOTE: Only commas separate the values, NO Carriage Returns or
Line Feeds separate the values.
Step E. Un-address UPC.
101
SECTION 5
REMOTE OPERATION
FORM,3,
COUPLing,DIRECT,
XFMRRATIO,1.0,
FREQuency,60,
VOLTage1,115,
VOLTage2,115,
VOLTage3,115,
CURRent:LIMit,10
PHASe2,120,
PHASe3,240,
WAVEFORM1,1,
WAVEFORM2,1,
WAVEFORM3,1,
EVENTS,0,
SEGment,1,
FSEG,60,
VSEG1,120,
VSEG2,120,
VSEG3,120,
WFSEG1,1,
WFSEG2,1,
WFSEG3,1,
TSEG,.01,
LAST<eos>