Invert Setpoint - Siemens SINAMICS G120D Operating Instructions Manual

Distributed inverter cu240d-2 control unit with encoder evaluation
Hide thumbs Also See for SINAMICS G120D:
Table of Contents

Advertisement

8.14.2

Invert setpoint

Function description
The function inverts the sign of the setpoint using a binary signal.
Example
To invert the setpoint via an external signal, interconnect parameter p1113 with a binary signal
of your choice.
Table 8-33
Parameter
p1113 = 722.1
p1113 = 2090.11
Parameter
Number
p1113[C]
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
Application examples showing how a setpoint is inverted
Description
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Converter inverts the setpoint.
Inverts the setpoint via the fieldbus (control word 1, bit 11).
Name
BI: Setpoint inversion
Advanced commissioning
8.14 Setpoint processing
Factory setting
Dependent on the
converter
205