Advanced commissioning
8.17 Electrically braking the motor
8.17.3

Braking with regenerative feedback to the line

Overview
The typical applications for braking with energy recovery (regenerative feedback into the line
supply) are as follows:
• Hoist drives
• Centrifuges
• Unwinders
For these applications, the motor must brake for longer periods of time.
The converter can feed back up to 100% of its rated power into the line supply (referred to "High
Overload" base load).
Parameter
Setting the braking with regenerative feedback to the line
Parameter
Limiting the regenerative feedback for U/f control (p1300 < 20)
p0640[D]
Limiting feedback with vector control (p1300 ≥ 20)
p1531[D]
256
Performance ratings Power Module (Page 331)
Description
Current limit
Power limit, generating
Converter with the control units CU240D-2
Operating Instructions, 10/2020, FW V4.7 SP13, A5E34262100B AH
Factory setting
0 Arms
-0.01 kW