Deif SGC 410 User Manual page 78

Single genset controller
Table of Contents

Advertisement

Fault
The engine runs, but the controller
shows the genset to be OFF.
The controller shows incorrect PF
value or kW or load current.
The controller shows incorrect reading
for any of LOP, fuel level or engine
temperature sensors.
Table 15.2
Auto mode troubleshooting
Fault
The controller shows incorrect engine
RPM.
The controller does not start the engine
when a Remote start command is sent
from an external device.
Controller does not stop the engine when
a Remote stop command is sent from an
external device.
Table 15.3
Modbus troubleshooting
Fault
The controller is not sending data via the
Modbus communication
Table 15.4
Site monitoring troubleshooting
Fault
Site voltage is observed continuously
varying.
USER MANUAL 4189341243A UK
Action
Check the alternator voltage signal (L1 phase) is received by the controller terminal.
Check if the LOP and LLOP are working OK. Check the wiring to the controller.
Check wiring of the respective alternator phase voltage and the CT to the controller.
Check the CT ratio (if kW or current reading is faulty).
Check respective sensor and its wiring.
Check the SCP wiring.
Enter the Configuration mode in the controller and verify the calibration for the
respective sensor in the configuration.
Action
Check the wiring of the main alternator's L1-phase and neutral to the controller.
Check the wiring of the Remote start signal to the controller's respective digital
input terminal.
Enter the Configuration mode in the controller and verify the configuration for the
Remote start digital input terminal.
Check that the controller is in Auto mode.
Check for Mains monitoring disabled and Site mode disabled.
Check the wiring of the Remote stop signal to the controller's respective digital
input terminal.
Enter the Configuration mode in the controller and verify the configuration for the
Remote stop digital input terminal.
Check that the controller is in Auto mode.
Action
Check if the Modbus communication is enabled in the controller.
Check if the Modbus communication settings of slave match with the master.
Check if the connections are done properly for the Modbus input (terminals 31 and
32).
Check if the connections are interchanged.
Check the 120 Ω resistance between terminal A (terminal 31) and terminal B
(terminal 32).
Action
Check if panel and Site are properly earthed.
Check if the connections are done properly for the differential input (terminals 24
and 25).
Page 78 of 78