Running Modes; Auto Mode - Deif SGC 410 User Manual

Single genset controller
Table of Contents

Advertisement

7. Running modes

7.1 Auto mode

Select Auto mode with the Mode selection
Exercise Mode
Two scheduled sequences to start and stop the genset can be configured with SGC 410.
Exercise mode occurs when the controller is in Auto mode with no shutdown or warning alarms. In this mode, load transfer on
mains/genset is configurable. Scheduled sequences can be configured to repeat daily, weekly or monthly.
If the controller is in Auto mode, Exercise mode runs at the scheduled time for preset DG ON duration time. The controller exits
Exercise mode if the DG ON duration time expires or if the Stop/Config
If the controller is in Manual mode when the scheduled sequence begins, the genset will not start. If the controller is switched to
Auto mode during the Exercise, the genset will start and run for the remaining scheduled time.
The genset controller will not respond to a Remote start command in Exercise mode.
If both exercises are scheduled at the same time, the Start time for second exercise is increased by one minute.
Deep sleep mode
Deep sleep mode is a useful feature to extend the battery lifetime. This is done by suspending normal functions of the controller, and
place it in the lowest power consumption state. The controller maintains the status and alarms it had before Deep sleep mode.
When the controller wakes up, normal operations are resumed automatically.
The controller goes to Deep sleep mode when there is no user interaction for the preset Deep sleep mode delay time. The controller
does not go to Deep sleep mode when in Auto mode (Exercise) or when Modbus communication is enabled.
To wake the controller from Deep sleep mode, press:
Stop/Config
button
Start
button
Mode selection
button
Acknowledge
button
USER MANUAL 4189341243A UK
button.
button is pressed during a scheduled sequence.
Page 42 of 78

Advertisement

Table of Contents
loading