Deif SGC 410 User Manual page 50

Single genset controller
Table of Contents

Advertisement

No.
Alarms
4
Eng Temp - Ckt Opn
Low Fuel level (Sensor)
Low Fuel level (Switch)
5
Fuel level - Ckt Open
6
Fuel Theft
7
Low Water Level Switch
8
Shelter Temp - Ckt Open
9
Aux S2 - Ckt Open
Auxiliary Input (for example,
10
Aux_A - P)/user defined
name
11
Emergency Stop
12
Fail To Stop
13
Fail To Start
14
L1 Phase Over Voltage
15
L2 Phase Over Voltage
16
L3 Phase Over Voltage
17
L1 Phase Under Voltage
18
L2 Phase Under Voltage
USER MANUAL 4189341243A UK
Causes/Indication
The temperature sensor is not detected (circuit open).
Indicates that the amount of fuel level is below the preset
threshold. This condition is detected only when engine is
on.
Indicates that the amount of fuel level measured is low
through switch.
The fuel level sensor is not detected (circuit open).
The fuel consumption has exceeded the preset threshold.
Indicates that radiator water level is below the preset
threshold.
Shelter temperature sensor is not detected (circuit open).
Auxiliary sensor S2 is not detected (circuit open).
Configured auxiliary input has triggered longer than the
preset duration.
When emergency stop switch is pressed and immediate
shutdown is required.
It is detected that genset is still running after sending stop
command.
Indicates that genset has not started after the preset
number of start attempts.
Indicates that genset (L1) phase voltage has exceeded the
preset over-voltage threshold.
Indicates that genset (L2) phase voltage has exceeded the
preset over-voltage threshold.
Indicates that genset (L3) phase voltage has exceeded the
preset over-voltage threshold.
Indicates that genset (L1) phase voltage has fallen below
the preset under-voltage threshold.
Indicates that genset (L2) phase voltage has fallen below
the preset under-voltage threshold.
Actions
None
Shutdown
Warning
Electrical Trip
Notification
None
Shutdown
Warning
None
Shutdown
Warning
Electrical Trip
Notification
None
Shutdown
Warning
Electrical Trip
Notification
Warning
None
Shutdown
Warning
Electrical Trip
Notification
Notification
None
Shutdown
Warning
Electrical Trip
Notification
None
Shutdown
Warning
Electrical Trip
Notification
Shutdown
Shutdown
Shutdown
Shutdown
Warning
Shutdown
Warning
Shutdown
Warning
Shutdown
Warning
Shutdown
Warning
Page 50 of 78