Deif SGC 410 User Manual page 25

Single genset controller
Table of Contents

Advertisement

Level 2
(FLS) Notification Threshold
(NOTIFICATION THRESHOLD)
(FLS) Fuel Tank Capacity
(FUEL TANK SIZE)
(FLS) Fuel Theft Warning
(FUEL THEFT ALARM)
(FLS) Fuel Theft Alarm Threshold
(FUEL LVL THRESH)
(FLS) Circuit Fault Action
(OPEN CKT ALARM)
(FLS) Fuel Sensor Reference
(FUEL LVL REF)
(FLS) Fuel Level Sensor Calibration Table
Table 6.12
Analogue Input 3 (ENG TEMP / DIG L)
Level 2
Use Input As
(SENSOR SELECTION)
(Digital) Source
((DIG) SOURCE)
Name
(NAME)
(Digital) Polarity
((DIG) POLARITY)
(Digital) Action
((DIG) ACTION)
(Digital) Activation
((DIG) ACTIVATION)
(Digital) Activation Delay
((DIG) ACTIVATION DELAY)
(ETS) Circuit Fault Action
(OPEN CKT ALARM)
(ETS) Engine Temperature Sensor Calibration Table
USER MANUAL 4189341243A UK
Range
2 to 80 %
2 to 1000 litre
Enable
Disable
1 to 100 % per hour
None
Notification
Warning
Electrical Trip
Shutdown
Battery Negative
Engine Body
Resistance: 0 to 5000 Ω
Fuel level: 0 to 100 %
Range
Not used
Digital Input L
Engine Coolant Temperature Sensor
See Digital input source selection in this document
Auxiliary Input L
Close to Activate
Open to Activate
None
Notification
Warning
Electrical Trip
Shutdown
Never
From Engine Start
From Monitoring On
Always
1 to 180 s
None
Notification
Warning
Electrical Trip
Shutdown
Resistance: 0 to 5000 Ω
Temperature: -25 to 300 °C
Page 25 of 78