Deif SGC 410 User Manual page 36

Single genset controller
Table of Contents

Advertisement

Level 2
Over-speed Threshold
(OVER SPEED THRESH)
Over-speed Delay
(OVER SPEED DELAY)
Gross Over-speed Threshold
(GROSS OS THRESHOLD)
Table 6.32
Battery Monitoring (BATTERY MONITOR)
Level 2
Low Battery Voltage Action
(LOW VOLT ACTION)
Low Battery Voltage Threshold
(LOW VOLT THRESHOLD)
Low Battery Voltage Delay
(LOW VOLT DELAY)
High Battery Voltage Action
(HIGH VOLT ACTION)
High Battery Voltage Threshold
(HIGH VOLT THRESHOLD)
High Battery Voltage Delay
(HIGH VOLT DELAY)
Table 6.33
Charging Alternator Monitoring (CHARGE ALT MON)
Level 2
Charging Alternator Fail Action
(FAIL ACTION)
Charging Alternator Fail Threshold
(FAIL THRESHOLD)
Charging Alternator Fail Delay
(FAIL DELAY)
Table 6.34
Preheating (PREHEAT)
Level 2
Pre-heat Timer
(PREHEAT TIMER)
Engine Temperature
(ENG TEMP EN)
Engine Temperature Threshold
USER MANUAL 4189341243A UK
Range
700 to 4000 RPM
1 to 20 s
100 to 200 %
Range
None
Notification
Warning
Electrical Trip
Shutdown
8.0 to 31.0 V
5 to 1800 s
None
Notification
Warning
Electrical Trip
Shutdown
9.0 to 32.0 V
5 to 1800 s
Range
None
Notification
Warning
Electrical Trip
Shutdown
0.0 to 35.0 V
5 to 60 s
Range
1 to 900 s
Enable
Disable
10 to 300 °C
Page 36 of 78