Wiring - Deif SGC 410 User Manual

Single genset controller
Table of Contents

Advertisement

TSC1 SA Torque Speed Control
Torque Speed Control 1 (TSC1) is the speed control signal from the SGC to the ECU. For known protocols, the SGC uses the
expected source address when TSC1 SA is -1 (default value). You can configure the controller for a specific source address (the
range is 0 to 255). Ask the engine manufacturer to verify the TSC1 source address.

13.7 Wiring

More information
See the Installation chapter for more information about wiring.