Deif SGC 410 User Manual page 22

Single genset controller
Table of Contents

Advertisement

Level 2
(BATTERY MON)
Low Voltage Threshold
(LOW BATT THRESHOLD)
Battery Monitoring Delay
(LOW BATT MON DELAY)
Genset Run Duration
(GEN RUN DURATION)
Table 6.5
Cyclic Mode (CYCLIC CONFIG)
Level 2
Cyclic Mode
(CYCLIC MODE)
Genset Off Time
(GEN OFF DURATION)
Genset On Time
(GEN ON DURATION)
Table 6.6
Auto Exercise – Event 1 (AUTO EXERCISE – 1)
Level 2
Auto Exercise
(EVENT 1)
Event Occurrence
(EVENT OCCURENCE)
Event Day
(EVENT DAY)
Start Time
(START TIME)
Duration
(GEN ON DURATION)
Load Transfer
(LOAD TRANSFER)
Table 6.7
Auto Exercise – Event 2 (AUTO EXERCISE – 2)
Level 2
Auto Exercise
(EVENT 2)
Event Occurrence
(EVENT OCCURENCE)
Event Day
(EVENT DAY)
Start Time
(START TIME)
USER MANUAL 4189341243A UK
Range
Disable
12.0 to 60.0 V
5 to 300 s
1 to 720 min.
Range
Enable
Disable
1 to 720 min.
1 to 720 min.
Range
Enable
Disable
Daily
Weekly
Monthly
Daily: Runs every day
Weekly: Sunday to Saturday
Monthly: 1 to 28
00:00 to 23:59 hour
00 hr 01 min. to 99 hr 59 min.
Enable
Disable
Range
Enable
Disable
Daily
Weekly
Monthly
Daily: Runs every day
Weekly: Sunday to Saturday
Monthly: 1 to 28
00:00 to 23:59 hour
Page 22 of 78