7.2 Manual mode

Module Operation in Manual Mode
DG OFF
Start button
Warm up
Warm up delay expired
DG ON
Stop button
Engine
cooling
Start the engine
Stop the engine
USER MANUAL 4189341243A UK
Engine
cooling
Shutdown Alarm
Warning Alarm
Notification
Shutdown Alarm
Warning Alarm
Notification
Press the Stop/Config
Press the Start
button to crank the engine
If the Start
button is pressed in this mode, the
controller sends a Start command and the genset starts
according to the Start sequence. When the genset loading
voltage and frequency are above the Minimum healthy
thresholds, the Warm-up delay timer starts. At the end of
the Warm-up delay, the Load transfer delay starts and the
genset latches. The running hours stop increasing when a
Stop command is received.
Press the Stop/Config
engine.
Press the Stop/Config
engine immediately.
When the Stop/Config
controller opens the genset contactor, and the Engine
cooling time starts. At the end of the Engine cooling time,
the controller initiates the Stop sequence by giving the
Stop command.
If the Stop/Config
button is pressed during Engine
cooling time, the controller skips the Cooling time and
sends the Stop command immediately.
button.
button to stop the running
button twice to stop the
button is pressed, the