Table 29: Scaling Menu Item - WAGO 750-496 Manual

8ai 0/4-20ma s.e., 8-channel analog input; 0/4-20 ma, single-ended
Hide thumbs Also See for 750-496:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.

Table 29: Scaling Menu Item

Option
Channel x
Activate factory scaling
Activate user scaling
Current [mA]
Process value (dec)
Process value (hex)
*)
Factory setting
Description
Factory scaling is activated (no effect).
*)
Factory scaling is deactivated (no effect).
Gain
The Gain value is specified by the manufacturer.
Offset
The Offset value is specified by the manufacturer.
User-defined scaling is active. By activating this setting you can
also specify the individual gain and offset values.
*)
User scaling is deactivated. Individually specified gain and offset
values cannot be entered.
Enter the Gain value for the user scaling.
Gain
The Gain value is used as a gain factor on the process value.
The value entered must fall within the value range 0 ... 65535.
The resolution is 1/1024.
Enter the Offset value for the user scaling.
The Offset value causes a zero offset of the process value (shift
Offset
along the Y axis).
The value entered must fall within the value range
−32768 ... 32767.
Display of the calibrated input current in milliamps (mA).
This is a 32-bit value.
If the channel is deactivated, "N/A" (not available) is displayed.
The input current value is read cyclically from the I/O module.
Display of the process value for the channel selected in decimal notation.
If the channel is deactivated, "N/A" (not available) is displayed.
The process value is read cyclically from the I/O module.
Display of the process value for the channel selected in hexadecimal
notation.
If the channel is deactivated, "0x7FFF" (not available) is displayed.
The process value is read cyclically from the I/O module.
Commissioning
57