Special Format; Sensor Type 0; Table 22: Process Image, Sensor Type 0 - WAGO 750-496 Manual

8ai 0/4-20ma s.e., 8-channel analog input; 0/4-20 ma, single-ended
Hide thumbs Also See for 750-496:
Table of Contents

Advertisement

36
Process Image
4.3.3

Special Format

4.3.3.1
Sensor Type 0 ... 20 mA
For the current measurement with sensor type 0 ... 20 mA, the input range of
0 ... +20 mA is mapped to a process value rage of 0 ... +32767. The current
underranges and overranges refer to manufacturer range violations.
Table 22: Process Image, Sensor Type 0 ... 20 mA, Amount/Sign Format
Input current
mA
< 0
Underrange
0.0
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0
Overrange
> 20.0
Short circuit
> 21.0
1)
Status bits: X: not used, F= error, Ü= overflow
2)
When underrange / overrange limit is ON
3)
When short circuit diagnostics is ON
Manual
Version 1.2.2
Numeric value
Binary
'0000.0000.0000.0 011'
2)
'0000.0000.0000.0 000'
'0000.1111.1111.1 000'
'0001.1111.1111.1 000'
'0010.1111.1111.1 000'
'0011.1111.1111.1 000'
'0100.1111.1111.1 000'
'0101.1111.1111.1 000'
'0110.1111.1111.1 000'
'0111.1111.1111.1 000'
2)
'0111.1111.1111.1 011'
3)
'0111.1111.1111.1 011'
750-496 8AI 0/4-20mA S.E.
1)
XFÜ
Hex.
Dec.
0x0003
3
0x0000
0
0x0FF8
4088
0x1FF8
8184
0x2FF8
12280
0x3FF8
16376
0x4FF8
20472
0x5FF8
24568
0x6FF8
28664
0x7FF8
32760
0x7FFB
32763
0x7FFB
32763
WAGO-I/O-SYSTEM 750
Status
Byte
Error LED
Hex.
0x41
ON
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x50
ON

Advertisement

Table of Contents
loading