Figure 23: Channel Settings Menu Item View; Table 28: Channel Settings Menu Item - WAGO 750-496 Manual

8ai 0/4-20ma s.e., 8-channel analog input; 0/4-20 ma, single-ended
Hide thumbs Also See for 750-496:
Table of Contents

Advertisement

54
Commissioning

Figure 23: Channel settings Menu Item View

Table 28: Channel settings Menu Item

Option
General Settings
Sensor type
Software low pass filter
ON
Diagnostics
Show measurement
overrange
Manual
Version 1.2.2
Description
Channel deactivated
0 ... 20 mA
*)
4 ... 20 mA
3.6 ... 21 mA (NAMURNE43) Measurement range +3.8 ... +20.5 mA
The software low pass filter is activated.
*)
The software low pass filter is deactivated.
*)
The "Measurement Overrange" is activated and is displayed in
the status byte.
The "Measurement Overrange" diagnosis function is deactivated
and not displayed in the status byte.
WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.
The channel selected in the main menu is
deactivated.
If the channel is deactivated, "0x7FFF"
appears in the Monitoring menu item
under process value "N/A" (not available)
and under hexadecimal process value.
Measurement range 0 ... +20 mA
Measurement range +4 ... +20 mA