WAGO 750-496 Manual page 87

8ai 0/4-20ma s.e., 8-channel analog input; 0/4-20 ma, single-ended
Hide thumbs Also See for 750-496:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.
Table 49: General module / channel parameters
Parameter
Process alarm:
User limit value
violation
Channel x (x = 0 ... 7)
Lower user limit
Upper user limit
*)
Factory setting
Value
0 (false)
*)
1 (true)
*)
−32768
... 32767
*)
−32768 ... 32767
Explanation
Falling below the lower or above the upper user
limit on the respective signal channel does not
lead to transmission of a process alarm. The
lower and upper user limits are set in another
attribute.
Provided that the channel diagnostics of the
respective signal channel has been activated,
falling below the lower or above the upper user
limit leads to transmission of a process alarm.
No entry in the diagnostics database of the
station proxy is made. The lower and upper user
limits are set in another attribute.
Based on the value range of the input signal, a
lower limit value of the input signal can be
specified that can lead to the abovementioned
event of a process alarm.
Based on the value range of the input signal, an
upper limit value of the input signal can be
specified that can lead to the abovementioned
event of a process alarm.
Appendix