installation
FLUEING INTRODUCTION (END OF LINE POWER FLUE)
The GF950L uses the "balanced flue" technology Co-Axial system. The inner liner flues products of combustion to the outside while the outer liner draws outside
combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and flue system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or
gas burning appliance. Each direct vent gas appliance must use it's own separate flue system. Common flue systems are prohibited.

FLUEING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS

END OF LINE HORIZONTAL POWER FLUE FLUE CHART
Note: Rigid pipe is approved for up to 18m.
Note: Flex pipe is approved for up to 12m using 2 X 946-756 - 6m flex kits.
The gas power flue system is designed to allow the installation of a gas appliance when typical natural flue configurations are not possible. Must be
terminated horizontally. Vertical terminations are not permitted.
18m Overall length Max.
Shown with 3 - 90
Important:
Maximum total flue length = 18m maximum of six - 90° elbows permitted.
One 90° elbow = two 45° elbows.
Maximum total negative flue length = 2m.
Minimum (1.22 m) from the unit prior to terminating.
Note: Maximum length of 18m is based on overall length of combined
chimney components.
Do not run positive flueing after a negative run.

FLUE RESTRICTOR POSITION

60
18m Overall length Max.
Shown with 5 - 90
0
elbows
Restrictor - Set 3 - 18mm open
0
elbows
Shown with 2 elbows (Negative run 18m)
18m Run (no rise)
Power Flue Aeration:
NG: 4.4 mm
Propane: 11 mm
ULPG: 13 mm
NOTE: Ensure aeration is set to correct configuration.
This negative run is for the end of
line power flue cap only. Do not run
with the inline power flue.
Regency GF950L-2 Gas Fireplace