FLUEING INTRODUCTION (INLINE POWER FLUE)
Venting Arrangements for Horizontal Terminations
The GF950L uses the "balanced flue" technology Co-Axial system. The inner liner flues products of combustion to the outside while the outer liner draws
Inline Horizontal Vent Chart
outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
Note: Rigid pipe is approved for up to 60 feet (18m).
The gas appliance and flue system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or
Note: Flex pipe is approved for up to 40 feet (12m) using 2 X 946-756 - 20 foot (6m) flex kits.
gas burning appliance. Each direct vent gas appliance must use it's own separate flue system. Common flue systems are prohibited.
The gas power vent system is designed to allow the installation of a gas appliance when typical natural vent configurations (shown in this manual)
IMPORTANT:The inline power flue must be installed within the confines of the home/structure and must be accessible for future servicing. An access hole as
are not possible.
noted in this manual or an attic space would be suitable.
FLUEING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS

INLINE HORIZONTAL FLUE CHART

Note: Rigid pipe is approved for up to 18m.
Note: Flex pipe is approved up to 12m using 2x946-756 - 6m flex kits.
Minimum 1 ft (0.3 m)
following an elbow
The gas power flue system is designed to allow the installation of a gas applianace when typical natural flue configurations (shown in this manual) are not
possible.
Minimum 0.3m
following an elbow
18m Overall length Max.
Shown with 3 - 90
Minimum 4 ft (1.2 m)
Minimum 1.8 m rise from top of appliance if there is a negative run
from the unit
Minimum 1.2m
Important:
from the unit
Maximum total vent length = 60' (18m) maximum of six - 90° elbows
permitted. One 90° elbow = two 45° elbows.
Maximum total negative vent length = 7' (2m).
Important:
Note: Maximum length of 60 feet (18m) is based on overall length of
Maximum total flue length = 18m maximum of six - 90° elbows permitted.
combined chimney components.
One 90° elbow = two 45° elbows.
Maximum total negative flue length = 2.1m.
Do not run positive venting after a negative run.
Minimum 1.8 m rise from top of appliance if there is a negative run.
Note: Maximum length of 18 meters is based on overall length of com-
bined chimney components.
Vent Restrictor Position
Do not run positive flueing after a negative run.

FLUE RESTRICTOR POSITION

Regency GF950L-2 Gas Fireplace
920-210
Inline Power Vent Vertical or Hortizontal Installation Instructions
60' (18m) Overall length
Max. Shown with 5 - 90
elbows
18m Overall length Max.
Shown with 5 - 90
elbows
0
Restrictor - Set 3 - 18mm open
Restrictor - Set 3 - 18mm open
60' (18m) Overall length
Max. Shown with 3 - 90
0
elbows
60' (18m) Run (no rise)
elbows
0
18m Run (no rise)
3 1 8 "
0
Minimum 1 ft (0.3 m)
prior to an elbow
Maximum allowable negative run 7 ft (2.1 m)
Minimum 0.3 m
prior to an elbow
Maximum allowable negative run 2.1m
Inline power vent location restrictions:
Minimum 4 ft (1.2 m) from the unit
Minimum 1 ft (0.3 m) prior to an elbow.
Minimum 1 ft (0.3 m) following an elbow.
Minimum 1 ft (0.3 m) prior to a termination cap.
Inline power flue location restrictions:
When the inline blower is installed after a negative run, for every foot of
Minimum 1.2 m from the unit
negative run the inline blower must be an equal distance or greater from the
Minimum 0.3 m prior to an elbow.
90-degree elbow. See example above.
Minimum 0.3 m following an elbow.
Minimum 0.3 m prior to a termination cap.
When the inline blower is installed after a negative run, for every foot of
negative run the inline blower must be an equal distance or greater from the
90-degree elbow. See example above.
1
Minimum 1 ft (0.3 m)
prior to a termination
cap
Minimum 0.3 m
prior to a termination
cap
** Inline blower when installed after a negative
run must be an equal distance or greater from a
90 degree elbow. (Example: In a 3-foot (0.9m)
negative run, the inline power vent must be a
minimum of 3 feet (0.9m) away from the elbow.)
**Inline blower when installed after a negative
run must be an equal distance or greater
from a 90 degree elbow. (Example: In a 0.9m
negative run, the inline power flue must be a
minimum of 0.9m away from the elbow.)
Inline Power Flue Bypass Setting:
25.4 mm
Burner Aeration Setting:
NG: 4.4mm
Propane: 11mm
ULPG: 13mm
NOTE: Ensure aeration is set to correct configura-
tion.