ID50 Series Panel - Installation, Commissioning & Configuration Manual
[S1 Device]
1 : Sensors
[Sensor nn - AVS]
Select Type :
1 : AVS
2 : AVR
or
1
A2.2 Learning Individual VIEW
When installed on a loop from the ID60 Panel, each
VIEW
(AVS) type by default. This may then be configured as
Advanced VIEW
A VIEW
any sensor but has an additional Type configuration
option. The procedure to configure the sensor type is as
follows:
1 Using the numeric keypad, press
2 : Modules
2 At the prompt, using the numeric keypad enter the
1
[Sensor]
3 The LCD then shows current settings and editable
Note: Use
[Sensor nn - AVS]
3 : Sensitivity
4 The LCD then displays the VIEW
2
< : Cancel
2
[Sensor nn - AVR] 1 : Zone (nn)
3 : Sensitivity
A2 - 3
sensor is assigned the Advanced VIEW
TM
Reference (AVR) type.
TM
sensor may be learnt in the same manner as
TM
sensors configuration option.
address of the VIEW
sensor to be edited and confirm
TM
using
.
5
Enter Address ____
parameters. Using the numeric keypad, press
select the Type option.
/
to select the next/previous address
2
8
respectively.
1 : Zone (nn)
4 : [
Blank/Existing Text
selection menu. Using the numeric keypad, press
or
to select the AVS or AVR type respectively.
2
The display automatically returns to the previous
menu, as shown below:
4 : [
Blank/Existing Text
Sensors
TM
Sensor
TM
to select the
1
to
2
2 : Type
]
device type
TM
1
2 : Type
]
997-263, Issue 4
September 2002