ID50 Series Panel - Installation, Commissioning & Configuration Manual
1
or
2
8
6
5.5.18 Digital Input 1
Digital Input 1 can be configured as either Day Mode Start
or Class Change function.
When configured as Day Mode Start, activation from the
input during the Day Mode period starts/ends Day Mode
delays, depending on their current state.
When Class Change is selected outputs assigned to CBE
Rules that have Class Change configured will activate
when Digital Input 1 is operated.
To configure Digital Input 1:
1 Using the numeric keypad, press
Commissioning menu to enter the Setup menu.
[Setup] Language =
> : Change
2 Press either
2
the Digital Input 1 menu is displayed.
[Setup]
Digital Input 1 =
> : Change
3 Press
to toggle between Day Mode Start and
6
Class Change.
[Setup]
Digital Input 1 =
> : Change
4 With the required configuration of Digital Input 1
displayed, press
menu.
47
1
English
× : More
< : Exit
/
to step through the options until
8
Day Mode Start
× : More
< : Exit
Class Change
× : More
< : Exit
to return to the Commissioning
4
997-263, Issue 4
September 2002
at the