ID50 Series Panel - Installation, Commissioning & Configuration Manual
997-263, Issue 4
September 2002
A2.3 Changing VIEW
The following procedure describes how to configure the
sensitivity levels for alarm (alarm and pre-alarm), day
(alarm and pre-alarm) and sensor grouping for a VIEW
sensor.
1 Follow the procedure in Section A2.2, Learning
Note: Use the
[Sensor nn - AVS]
3 : Sensitivity
2 The LCD then displays the VIEW
3
[Sensor nn - AVS]
1 : Alarm(L5,5)
3 To change the Alarm; Day or AVSGroup options,
1
[Sensor nn - AVS]
Enter new alarm level : ____
4 Using the numeric keypad enter the required alarm
[Sensor nn - AVS]
Enter new prealarm level : ____
5 Enter the required prealarm value 0 to 9, and press
Day Mode Levels
The Day option alarm levels are changed in the same
manner as the Alarm option.
Using the numeric keypad, press
option, then follow the procedure above.
A2 - 4
Sensor Sensitivity
TM
Individual VIEW
Sensors to access the sensor
TM
configuration menu. The LCD shows current settings
and editable parameters. Using the numeric keypad,
press
to select the Sensitivity option.
3
/
buttons to select the previous/
2
8
next address respectively.
1 : Zone (nn)
4 : [
Blank/Existing Text
menu. The sensitivity is displayed as two values in
brackets. The first signifies the alarm level (default
L5), and the second the pre-alarm level (default 5).
Sensitivity
2 : Day(L5,5)
3 : AVSGroup(01)
using the numeric keypad press
respectively. If
(Alarm) is pressed the LCD
1
prompts for a new alarm level as follows:
Sensitivity
value 1 to 9, and press
5
automatically prompts for the pre-alarm value as
follows:
Sensitivity
to confirm. The LCD then automatically returns
5
to the VIEW
sensor Sensitivity menu.
TM
TM
2 : Type
]
sensor Sensitivity
TM
,
or
1
2
3
< : Cancel
to confirm. The LCD then
< : Cancel
to access the Day
2