1
6
1
or
2
8
6
5
5.5.2 Date Format
This option is used to select one of three available date formats
for display on the LCD. The options available are dd/mm/yyyy,
mm/dd/yyyy or yyyy/mm/dd. To change the date format:
1 From the Commissioning menu, press the ‘
on the numeric keypad to enter the Setup menu. The
LCD shows the Language menu.
[Setup] Language =
> : Change
Press the ‘
/
2
8
menu until the Date Format menu is displayed.
2 Press the ‘
’ button to step through the alternative
6
Date Format settings.
[Setup]
Date Format = mm/dd/yyyy
> : Change
[Setup]
Date Format = yyyy/mm/dd
> : Change
[Setup]
Date Format = dd/mm/yyyy
> : Change
3 Press ‘
’ to return to the Commissioning menu.
4
5.5.3 Primary/Extend Delay Timers
The Primary Delay Timer allows an initial investigation time
of up to 300 seconds (default 30 seconds) to be entered or
changed. The Extend Delay Timer allows an additional delay
(default - 3 minutes) to be entered or changed. The total
delay time cannot exceed 10 minutes. To set delay times:
1 From the Commissioning menu, press the ‘
on the numeric keypad to enter the Setup menu.
[Setup] Language =
> : Change
2 Press the ‘
/
2
menus to display the Primary Delay Time menu.
[Setup]
Primary Delay Time = 30 Seconds
> : Change
3 Press the ‘
’ button. The display then prompts you
6
for the new value:
[Setup]
Primary Delay Time = 30 Seconds
Enter new value ____
4 Enter the required delay time using the numeric
buttons; (e.g. to set the delay time to the maximum
value of 300 seconds, first enter ‘3’, then enter ‘0’, ‘0’).
[Setup]
Primary Delay Time = 30 Seconds
Enter new value 300
5 Press the ‘
’ button to confirm and return to the
5
Setup menus.
6 Repeat steps 1 to 5 for the Extend Delay Time, using
the Extend Delay Time display and a maximum value
of 10 minutes.
39
English
× : More
< : Exit
’ buttons to scroll through the Setup
× : More
< : Exit
× : More
< : Exit
× : More
English
× : More
< : Exit
’ buttons to step through the Setup
8
× : More
< : Cancel
3
: Confirm
< : Cancel
3
: Confirm
< : Cancel
997-263, Issue 4
September 2002
’ button
1
< : Exit
’ button
1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Id60

Table of Contents