4.3 Internal Checks

When all PCBs have been installed and all cabling has
been successfully checked, the appropriate jumper links
may need to be configured, as described below.
4.3.1 Jumper Link Options
SND Jumper (J7 / J6 / J8)
SND
The SND Jumper link is the default position for the 6-way
link. Removing the link from the SND jumper disables
the normal operation of the outputs - for normal panel
operation this link should not be removed. The jumper is
situated to the left of the Loop terminal block (TB5) at the
top of the PCB.
ÜE Jumper (J12 / J10 / J11)
Not supported in standard operation.
Software Upgrade (J4)
The Software Upgrade Jumper in conjunction with the
Upgrade kit is used to upgrade the panel operating
software. To enable the panel upgrade, fit a link to J4
and connect the appropriate cable. The link J4 must be
removed on completion of the upgrade (see 997-415,
ID50 Series Panel - Upgrading Instructions). This
jumper is situated to the right of the Digital/ÜE terminal
block (TB8).
Configuration Lock (J9)
DISABLED
The Configuration Lock Jumper is used to lock and unlock
J4
the system configuration. If the link is fitted the system
configuration is locked and changes will NOT be allowed.
FLASH PRG
If the link is removed system configuration is possible.
ENABLE
The panel can only be configured with the Configuration
Lock (J9) in the unlocked position. The jumper is situated
to the left of the Digital / ÜE terminal block (TB8).