ID50 Series Panel - Installation, Commissioning & Configuration Manual
1
or
2
8
6
5.5.14 Repeater Protocol
This option is used to select one of two available protocol
formats when repeaters are connected to the panel via
the RS485 communications link. The options available
are:
a. NOTIFIER
b. ARP50/RP50.
The NOTIFIER protocol supports the IDR-2A and IDR-2P
Repeaters.
There are two additional options:
c. Third party equipment connection at the RS485 link.
d. DISABLED, disables communication to any device
connected to the panel.
To change the Repeater Protocol:
1 From the Commissioning menu, press the ‘
on the numeric keypad to enter the Setup menu.
[Setup] Language =
> : Change
2 Press the ‘
/
2
8
menu until the Repeater Protocol menu is displayed.
[Setup] Repeater Protocol = NOTIFIER
> : Change
3 Press the ‘
’ button repeatedly to step through the
6
alternative protocol settings.
[Setup] Repeater Protocol = NOTIFIER
> : Change
[Setup] Repeater Protocol = ARP50/RP50
> : Change
4 Press ‘
’ to return to the Commissioning menu.
4
45
1
English
× : More
< : Exit
’ buttons to scroll through the Setup
× : More
< : Exit
× : More
< : Exit
× : More
< : Exit
997-263, Issue 4
September 2002
’ button