ID50 Series Panel - Installation, Commissioning & Configuration Manual
997-263, Issue 4
September 2002
5.5.4 Extinguishing System Delay
The extinguishing system delay allows an evacuation period
of up to 180 seconds to be entered (default 60 secs, minimum
of 10 secs). To configure the delay, proceed as follows:
1 From the Commissioning menu, press the ‘
on the numeric keypad to enter the Setup menu.
[Setup] Language =
> : Change
2 Press the ‘
/
2
menus to display the Ext. System Delay menu.
[Setup]
Ext. System Delay =
> : Change
3 Press the ‘
’ button. The display then prompts you
6
for the new value:
[Setup]
Ext. System Delay =
Enter new value __
4 Enter the required delay time using the numeric
buttons, e.g. 30 secs:
[Setup]
Ext. System Delay =
Enter new value 30
5 Press the ‘
’ button to confirm and return to the
5
Setup menus.
5.5.5 Extinguishing System Soak
To specify for how long the extinguishing system operates
for after being turned on:
Note: The timer will only be triggered by CBE rules that
have the Soak Timer Enable activated.
1 From the Commissioning menu, press the ‘
on the numeric keypad to enter the Setup menu.
[Setup] Language =
> : Change
2 Press the ‘
/
2
menus to display the Ext. System Soak menu.
[Setup]
Ext. System Soak =
> : Change
3 Press the ‘
’ button. The display then prompts you
6
for the new value:
[Setup]
Ext. System Soak =
Enter new value __
4 Enter a delay time using the numeric buttons, between
0 and 999 secs, e.g. 90 secs:
[Setup]
Ext. System Soak =
Enter new value 90
Note: Entering a value of ‘0’ means that the output, after
switching ON, is not switched OFF.
5 Press the ‘
’ button to confirm and return to the
5
Setup menus.
40
English
× : More
< : Exit
’ buttons to step through the Setup
8
60 Seconds
× : More
< : Exit
60 Seconds
3
: Confirm
< : Cancel
60 Seconds
3
: Confirm
< : Cancel
English
× : More
< : Exit
’ buttons to step through the Setup
8
0 Seconds
× : More
< : Exit
0 Seconds
3
: Confirm
< : Cancel
0 Seconds
3
: Confirm
< : Cancel
’ button
1
’ button
1