Notifier INERTIA-2464/64 Technical/Programming Manual
Notifier INERTIA-2464/64 Technical/Programming Manual

Notifier INERTIA-2464/64 Technical/Programming Manual

Fire indicator panel
Table of Contents

Advertisement

Quick Links

INERTIA-2464/64
Fire Indicator Panel
TECHNICAL & PROGRAMMING MANUAL
Revision 1.07e
A P P R O V A L S
Australian Standard AS1603.4 1987
Australian SSL Approval No 215
Australian SSL Quality Accredited
Hong Kong Fire Services Dept Approved.
PROC Standard GB4717-93
C-Tick Approval No. N1336
Serial No.
Date of Manufacture
7 COLUMBIA COURT
NORWEST BUSINESS PARK
BAULKHAM HILLS
NSW 2153
AUSTRALIA
Ph (02) 9899-4155
Fax (02) 9899-4156
E-mail: sales@inertia.com.au
http://www.inertia.com.au

Advertisement

Table of Contents
loading

Summary of Contents for Notifier INERTIA-2464/64

  • Page 1 INERTIA-2464/64 Fire Indicator Panel TECHNICAL & PROGRAMMING MANUAL Revision 1.07e A P P R O V A L S Australian Standard AS1603.4 1987 Australian SSL Approval No 215 Australian SSL Quality Accredited Hong Kong Fire Services Dept Approved. PROC Standard GB4717-93 C-Tick Approval No.
  • Page 2 Page i INERTIA-2464 Technical & Programming Manual COMPATIBLE DETECTORS Make Model Type Model Number Apollo Thermal Type A Series 60 Apollo Thermal Type B Series 60 Apollo Thermal Type C Series 60 Apollo Thermal Type D Series 60 Apollo Smoke Ionisation Series 60 Apollo...
  • Page 3: Table Of Contents

    INERTIA-2464 Technical & Programming Manual Page ii TABLE OF CONTENTS TECHNICAL MANUAL -------------------------------------------------------------------------------------- 1 SPECIFICATION ---------------------------------------------------------------------------------------------- 2 SYSTEM EXPANSION..................... 3 ENVIROMENTAL LIMITS ..................4 POWER SUPPLY RATINGS AND SETTINGS............4 BATTERY TYPE AND CAPACITIES ............... 5 TECHNICAL DESCRIPTION ------------------------------------------------------------------------------- 6 GENERAL ........................
  • Page 4 Page iii INERTIA-2464 Technical & Programming Manual NON LATCHING TYPE.................... 36 TIME DELAY AZF ....................37 APPENDIX B --------------------------------------------------------------------------------------------------- 38 ZONE OUTPUT CONFIGURATIONS..............38 APPENDIX C --------------------------------------------------------------------------------------------------- 39 ALARM VERIFICATION FACILITY (AVF) ............... 39 APPENDIX D --------------------------------------------------------------------------------------------------- 40 ANCILLARY TRIP (ACF)..................40 APPENDIX E --------------------------------------------------------------------------------------------------- 41 RELAY OUTPUT MAPPING ..................
  • Page 5: Technical Manual

    INERTIA-2464 Technical & Programming Manual Page 1 Section One TECHNICAL MANUAL Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 6: Specification

    Page 2 INERTIA-2464 Technical & Programming Manual SPECIFICATION Cabinet Zinc Sealed Steel 1.6mm Powder Coated Hinged Inner Door Hinged Outer Door Outside Dimensions 2464/24 750mm H x 390mm W x 160mm D 2464/32>64 750mm H x 780mm W x 160mm D Battery Box 280mm H x 390mm W x 160mm D AC Operational Voltage...
  • Page 7: System Expansion

    INERTIA-2464 Technical & Programming Manual Page 3 SYSTEM EXPANSION Zones Hardware Required Product Code Main Control board PCB-800 Main Termination board PCB-801L Zone Expansion board PCB-804G Zone Indicator board PCB-802 Main Control board PCB-800 Main Termination board PCB-801L Zone Expansion board PCB-804G Zone Indicator board PCB-802...
  • Page 8: Enviromental Limits

    Page 4 INERTIA-2464 Technical & Programming Manual Additional relay outputs: Relays Hardware Required Product Code Relay board containing 8 relays PCB-803 Relay board containing 8 relays PCB-803 Relay board containing 8 relays PCB-803 Relay board containing 8 relays PCB-803 Relay board containing 8 relays PCB-803 Relay board containing 8 relays PCB-803...
  • Page 9: Battery Type And Capacities

    INERTIA-2464 Technical & Programming Manual Page 5 PERFORMANCE DATA 27VDC Power Supply. AC Input 30 VAC +10% - 15% Output Current 3 AMPS (Incl 1A External) Output Voltage 27.6 VDC Current Limit 3 AMPS Output Ripple 50 mV Internal 5VDC 2A Power Supply. This supply's primary function is to power all internal operations of the FIP, ie: Microprocessor, liquid crystal display, LED's keypad etc.
  • Page 10: Technical Description

    Page 6 INERTIA-2464 Technical & Programming Manual TECHNICAL DESCRIPTION GENERAL The 2464 in its most basic form comprise of two boards, the main control board and the main termination board. The main control board contains the Microprocessor, EPROM, RAM and E ROM.
  • Page 11: Azf Description

    INERTIA-2464 Technical & Programming Manual Page 7 AZF DESCRIPTION The AZF's on the INERTIA-2464 are monitored and scanned by custom thick film hybrids. These hybrid IC's significantly reduce the possibility of false alarms and improve product efficiency and reliability. Alarm Zone loop resistance is the end of line resistor (EOLR 4K7) and any parallel connected detector. AZF SUPERVISORY CURRENT The supervisory current flows through the external terminal AZF+, through the field cable and to the end of line resistor (EOLR), returning to the panel at AZF- terminal.
  • Page 12: Printer Output

    Page 8 INERTIA-2464 Technical & Programming Manual PRINTER OUTPUT The printer port is designed to be used during testing and commissioning of the panel. The printer will report alarms and faults together with the date and time of the event, the printer can also be used during walk test mode to produce a history of the test and can be used to print current programming configuration.
  • Page 13: Alignment And Adjustment

    INERTIA-2464 Technical & Programming Manual Page 9 ALIGNMENT AND ADJUSTMENT INTERNAL 27VDC POWER SUPPLY If the on-board supply ONLY is being used (JP4 is linked) : With batteries disconnected and no alarms present, measure voltage across AUX 0V & AUX 24V on PCB801 and adjust the multi-turn potentiometer VR4 until voltage is 27.6V 1% (27.32V - 27.87V).
  • Page 14 Page 10 INERTIA-2464 Technical & Programming Manual IFS800 - JP3 DEFAULT (MEMORY RESET) Holding a short across these pins for 5 seconds during start-up causes the panel to reset to standard factory defaults. The panel will give 4 beeps after reset, to acknowledge default on startup. IFS800 - JP4 PROGRAM DISABLE When fitted, jumper between these pins to inhibit program changes.
  • Page 15: Placing Into Operation

    INERTIA-2464 Technical & Programming Manual Page 11 PLACING INTO OPERATION Suitably qualified technicians must install the panel. The following check procedures are recommended after every installation and prior to initial power-up. A thorough visual inspection should be made to every aspect of the fire panel. This includes loose wire strippings, metal filings, loose circuit boards, loose cabling, damage in transit etc.
  • Page 16: Functional Testing

    Page 12 INERTIA-2464 Technical & Programming Manual FUNCTIONAL TESTING Primary AC Supply Voltage: 200 or 220 or 240VAC +10% as required Charger Output Voltage without Batteries: 27.6V DC Keypad Functional Perform Auto Test LED's All Functional L.C.D Backlighting Functional Liquid Crystal Display Functional Zone Fault Detection Zone Alarm Detection Internal Sounder Operating...
  • Page 17: Fault Record

    INERTIA-2464 Technical & Programming Manual Page 13 FAULT RECORD FAULT CORRECTION DATE TESTS SATISFACTORILY COMPLETED. TESTED BY _______________________________ SIGNATURE _______________________________ DATE OF TEST ____________________________ If all faults have been rectified and all tests are completed satisfactorily, the 2464 fire indicator panel is now ready for operation.
  • Page 18: Instructions To Operators

    Page 14 INERTIA-2464 Technical & Programming Manual INSTRUCTIONS TO OPERATORS SUGGESTED ALARM PROCEDURE The following is a suggested alarm procedure for use by building fire officers or duty wardens. The fire indicator panel is designed for use by qualified fire fighters and it is strongly recommended that the fire panel not be operated in an emergency situation by other than suitably qualified fire fighters.
  • Page 19: Operator Instructions

    INERTIA-2464 Technical & Programming Manual Page 15 OPERATOR INSTRUCTIONS The functions of the INERTIA-2464 are divided into two (2) categories, • Global Functions • Zone Functions GLOBAL FUNCTIONS Global functions are those common to the overall system and are not specific to particular zones. Following is an explanation of their operation and the keystrokes required to perform the function required.
  • Page 20: Indicators

    Page 16 INERTIA-2464 Technical & Programming Manual INDICATORS Descriptor Colour Function Buzzer MAINS ON Green Illuminates when there is 200/220/240 VAC supply to the panel. BATT FAULT Yellow Illuminates if the battery fails a battery test. Illuminates if batteries are disconnected >30 seconds. Illuminates if batteries are short circuit >30 seconds.
  • Page 21: Battery Test

    INERTIA-2464 Technical & Programming Manual Page 17 BATT BATTERY TEST TEST This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a battery test as specified. The test will temporarily disconnect the batteries from the panel and apply load on the batteries for 60 seconds.
  • Page 22: Walk Test Mode

    Page 18 INERTIA-2464 Technical & Programming Manual WALK WALK TEST MODE TEST This function will place the panel into "walk test" mode. Walk test mode is used for the on-site testing of detector zones. This mode cannot be selected if any zone(s) is in alarm. Entry to walk test mode will be acknowledged by three beeps and the LCD will display "WALK TEST MODE".
  • Page 23: Silence/Acknowledge

    INERTIA-2464 Technical & Programming Manual Page 19 SILENCE SILENCE/ACKNOWLEDGE The purpose of the bells and internal buzzer, is to alert persons of a potential fire danger. Once the fire's location has been determined and appropriate measures are being taken, the firefighter may wish to silence the internal buzzer and bells without having to totally reset the alarm.
  • Page 24: Acf Isolate

    Page 20 INERTIA-2464 Technical & Programming Manual ACF ISOLATE ISOL Depressing the "ACF ISOL" key, will isolate the ACF (Ancillary output). The ACF isolated LED will illuminate and the ancillary output will not operate until the ancillary output is de-isolated. Pressing "ACF ISOL" for a second time will de-isolate the ancillary output.
  • Page 25: Zone Functions

    INERTIA-2464 Technical & Programming Manual Page 21 ZONE FUNCTIONS Zone functions are those relating specifically to the detection zones. Following is an explanation of their operation and the keystrokes required to perform the function required. ALARM TEST ENTER ALARM TEST The alarm test function momentarily disconnects the detector lines of the zone(s) under test and simulates a detector going into alarm, therefore testing the zone(s) alarm detection capability.
  • Page 26: Fault Test

    Page 22 INERTIA-2464 Technical & Programming Manual FAULT TEST ENTER FAULT TEST The fault test function momentarily disconnects the detection zone(s) under test and simulates the worst case condition for fault. A resistor load equal to worst case fault is placed on the zone continuously for 5 seconds then the zone is returned back to it's normal condition.
  • Page 27: Isolate

    INERTIA-2464 Technical & Programming Manual Page 23 ISOLATE ENTER ISOLATE The isolate function prevents the transmission of alarms or faults from the zones to the master alarm facility. The character "#" in the keystroke requires any one of the following entries; 1,2,3,4.., 63,64 or "ALL"...
  • Page 28: Reset

    Page 24 INERTIA-2464 Technical & Programming Manual RESET ENTER RESET The reset function momentarily disconnects power, and resets all alarm parameters for the zone(s) being reset. This returns the zone back to its "normal" state. The character "#" in the keystroke requires any one of the following entries; 1,2,3,4,5,6,7,8,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23,24 or "ALL"...
  • Page 29: Equipment As Fitted

    INERTIA-2464 Technical & Programming Manual Page 25 EQUIPMENT AS FITTED Description Code MAIN CONTROL BOARD PCB-800 MAIN TERMINATION BOARD PCB-801L OPTION ZONE EXPANSION BOARD PCB-802 OPTION ZONE INDICATOR BOARD PCB-804G OPTION ADD ON RELAY BOARD PCB-803 OPTION ADD ON OPEN COLLECTOR OUTPUT BOARD PCB-813 OPTION 100VA DOOR HOLDER P/SUPPLY TRANSFORMER...
  • Page 30: Programming Manual

    Page 26 INERTIA-2464 Technical & Programming Manual Section Two PROGRAMMING MANUAL Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 31: Programmable Options

    INERTIA-2464 Technical & Programming Manual Page 27 PROGRAMMABLE OPTIONS GLOBAL ANCILLARY TRIP LATCHING NORMALLY DE-ENERGISED NON-LATCHING NORMALLY DE-ENERGISED LATCHING NORMALLY ENERGISED NON-LATCHING NORMALLY ENERGISED ALARM VERIFICATION DISABLED 2 MINUTES 3 MINUTES 4 MINUTES 5 MINUTES TIME (DD) / (MM) / (YY) (HH) : (MM) ZONES DESCRIPTION...
  • Page 32: Defaults

    Page 28 INERTIA-2464 Technical & Programming Manual OUTPUT RELAYS Relays can be programmed to simulate: - • Isolate Relay • ACF Output • Brigade Relay #1 • Brigade Relay #2 • Fault Relay • Mains Fail Relay • General Alarm Relay •...
  • Page 33: Program Mode

    INERTIA-2464 Technical & Programming Manual Page 29 PROGRAM MODE TO ENTER PROGRAM MODE Hold the door switch down while pressing the following buttons in order shown to enter programming mode. PREVIOUS NEXT SELECT EXIT ENTER PROGRAMMING MODE The liquid crystal display will display all messages and prompts required to program the 2464 ONLY the "PREVIOUS","NEXT","SELECT","EXIT"...
  • Page 34 Page 30 INERTIA-2464 Technical & Programming Manual RELAYS TYPE MAPPING ISOLATE RELAY ANCILLARY OUTPUT (ACF) BRIGADE RELAY #1 BRIGADE RELAY #2 FAULT RELAY MAINS FAIL RELAY GENERAL ALARM RELAY BELL OUTPUT DOOR HOLDER RELAY MAP - AND (00)(00)(00)(00)(00) MAP - OR (00)(00)(00)(00)(00) MAP - FAULT (00)(00)(00)(00)(00)
  • Page 35 INERTIA-2464 Technical & Programming Manual Page 31 EXIT PROGRAMMING MODE SAVE CHANGES (NO) Use the "NEXT" & "PREVIOUS" keys to scroll through "YES" & "NO". Once the desired option has been highlighted, pressing the "SELECT" button will select it. Highlighting "YES" and pressing "SELECT" will write all changes made to the E ROM and the panel will then restart (this will drop any door holders / air-conditioning if connected).
  • Page 36 Page 32 INERTIA-2464 Technical & Programming Manual Once the desired option has been highlighted, pressing the "SELECT" button will select. Making a selection or pressing "EXIT" will return to zone selected. Note: The option previously set is displayed in brackets and is the first to be displayed. Previously set options will not be displayed if "ALL"...
  • Page 37 INERTIA-2464 Technical & Programming Manual Page 33 RELAY TYPE RELAY #ALL TYPE (GENERAL) Use the "NEXT" & "PREVIOUS" keys to scroll through: ISOLATE ANCILLARY BRIGADE 1 BRIGADE 2 FAULT MAINS FAIL GENERAL BELL DOOR HOLDER MAP -AND- MAP -OR- MAP –FAULT- MAP –ISOLATE- MAP -ISOLATE/FLT- DOOR SWITCH...
  • Page 38 Page 34 INERTIA-2464 Technical & Programming Manual GLOBAL PROGRAMMING (ACF) RELAY TIME Use the "NEXT","PREVIOUS" & "SELECT" keys to select. Pressing "EXIT" will return to "Main Menu". ACF OUTPUT ACF OUTPUT (NON-LATCH ND) Use the "NEXT" & "PREVIOUS" keys to scroll through: LATCHING ND NON-LATCH NE LATCHING NE...
  • Page 39 INERTIA-2464 Technical & Programming Manual Page 35 RELAY (GLOBAL RELAY UNITY MAP) MAP RELAY (XX) >> FROM ZONE (XX) Use the "NEXT" & "PREVIOUS" keys to change the first relay to start from, together with the matching zone. Use the “ENTER” key to toggle between the two and press “SELECT” once finalised. “Exit” will abort unity map.
  • Page 40: Latching Type

    Page 36 INERTIA-2464 Technical & Programming Manual APPENDIX A DESCRIPTION OF ALARM ZONE TYPES Different zone types can be selected using the programming mode. Each zone can be selected as any one of following: Type Description Input Delay Standard Latching 2 seconds Standard Latching 2 seconds with AVF...
  • Page 41: Time Delay Azf

    INERTIA-2464 Technical & Programming Manual Page 37 TIME DELAY AZF The time delay AZF zone can be preset to any one of 6 time delays in the initial setup. This type of zone is used for AS1668 smoke detection zones. Zone timing etc is as per AS1668-1991. Example: Timer #1 = 60 seconds Once the first alarm is received, the alarm LED is turned on steady;...
  • Page 42: Zone Output Configurations

    Page 38 INERTIA-2464 Technical & Programming Manual APPENDIX B ZONE OUTPUT CONFIGURATIONS Once a zone has alarmed, its output functions as programmed to one of the following output types. Type Output Description Indicate Only Indicate, Bell Indicate, Bell, General Alarm Indicate, Bell, General Alarm, Ancillary Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1 Indicate, Bell, General Alarm, Ancillary, Brigade Relay #2...
  • Page 43: Alarm Verification Facility (Avf)

    INERTIA-2464 Technical & Programming Manual Page 39 APPENDIX C ALARM VERIFICATION FACILITY (AVF) Alarm verification (AVF) is a facility used to minimise false alarms. It is also commonly referred to as a "CHECK- ALARM". GLOBAL PROGRAMMABLE OPTIONS AVF TIMEOUT Disabled 2 Minutes 3 Minutes 4 Minutes...
  • Page 44: Ancillary Trip (Acf)

    Page 40 INERTIA-2464 Technical & Programming Manual APPENDIX D ANCILLARY TRIP (ACF) The ancillary trip is used for the shutting down of air conditioning systems etc. in the event of a fire. GLOBAL PROGRAMMABLE OPTIONS ANCILLARY TRIP (ACF) NON-LATCHING ND LATCHING NON-LATCHING LATCHING...
  • Page 45: Relay Output Mapping

    INERTIA-2464 Technical & Programming Manual Page 41 APPENDIX E RELAY OUTPUT MAPPING A total of 64 expansion relays can be fitted to the INERTIA-2464. Each relay can be individually programmed to mimic any of the following; STANDARD OUTPUTS WHICH MAY BE MIMICED ANCILLARY OUTPUT (ACF) BRIGADE ALARM RELAY #1 BRIGADE ALARM RELAY #2...
  • Page 46: Isolate Mapping

    Page 42 INERTIA-2464 Technical & Programming Manual FAULT/ISOLATE MAPPING works the same as OR mapping of alarm except it relates to the fault/isolate flag on each zone instead of the alarm flag. This function will cause the relay to operate if any one of up to five (5) zones go into fault/put in isolate.
  • Page 47: Glossary Of Terms

    INERTIA-2464 Technical & Programming Manual Page 43 APPENDIX F GLOSSARY OF TERMS AS-1603.4 Australian standard for; - Automatic Fire Detection and Alarm Systems Control and Indicating Equipment. AS-1670 Australian standard for; - Automatic Fire Detection and Alarm Systems System Design Installation and Commissioning. AS-1668.1 Australian standard for;...
  • Page 48: Summary Of Terminations And Cautions

    Page 44 INERTIA-2464 Technical & Programming Manual APPENDIX G SUMMARY OF TERMINATIONS AND CAUTIONS. MCP LOOP Used for the looping of the manual call point to a particular zone chosen for indication. This is achieved by wiring from the zone, to the MCP, to the MCP loop then out to the field with the EOL across the last detector. The MCP is the first device on the circuit and both fault and alarm conditions will be indicated.
  • Page 49: Maf Isol & Transponder 0V

    INERTIA-2464 Technical & Programming Manual Page 45 MAF ISOL & TRANSPONDER 0V A 0V signal is switched back from the transponder test switch and is used for indication purposes at the FIP. This will indicate as MAF ISOLATED and initiate a common fault. It can also used for external devices to indicate a fault eg: evac amplifier speaker monitor.
  • Page 50: 2464 Programmed Options

    Page 46 INERTIA-2464 Technical & Programming Manual APPENDIX H 2464 PROGRAMMED OPTIONS Global System Parameters Date: Latch ND Non-Latch ND Latch NE Non-Latch NE ACF Output Disabled 2 min 3 min 4 min 5 min Alarm Verification (AVF) Notes: Programmed by Place an "X"...
  • Page 51 INERTIA-2464 Technical & Programming Manual Page 47 ZONE TYPE PROGRAMMING Date: AZF No. STD STD N/L Place an "X" in the appropriate box = Default Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 52 Page 48 INERTIA-2464 Technical & Programming Manual AZF No. STD STD N/L Place an "X" in the appropriate box = Default Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 53 INERTIA-2464 Technical & Programming Manual Page 49 ZONE OUTPUT PROGRAMMING Date: AZF No. INDICATE IBG- IBGA- IBGA- BR2 IBGA- BELL GENERAL BR1&BR2 Place an "X" in the appropriate box = Default Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 54 Page 50 INERTIA-2464 Technical & Programming Manual AZF No. INDICATE IBG- IBGA- IBGA- IBGA- BELL GENERAL BR1&BR2 Place an "X" in the appropriate box = Default Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 55 INERTIA-2464 Technical & Programming Manual Page 51 RELAY OUTPUT MAPPING Date: MAPPING MAINS BELL ISO/ FAIL Place an "X" in the appropriate box = Default Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 56 Page 52 INERTIA-2464 Technical & Programming Manual MAPPING MAINS BELL ISO/ FAIL Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 57: Technical Drawings

    INERTIA-2464 Technical & Programming Manual Page 53 APPENDIX I TECHNICAL DRAWINGS L2400_1 Presentation Drawing Rev A L2400_3 System ConFiguration Rev A E2400_1 Typical Output Connection Rev A 2464PS_3 External 3A Power Supply Rev C Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 59 INERTIA-2464 Technical & Programming Manual Page 1 Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 60 INERTIA-2464 Technical & Programming Manual Page 2 Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 61 INERTIA-2464 Technical & Programming Manual Page 3 Copyright (c) 1996, INERTIA FIRE SYSTEMS...
  • Page 62 Norwest Business Park This document is & shall remain the property of Drawn/ Engineer Baulkham Hills NSW 2153 3/1/1 G.W. Notifier Inertia Fire Systems Traced Design AUSTRALIA Unauthorised use of this 61 2 9894 1444 document in any way is Drg.

Table of Contents